51
Function description
Heating circuit control
(cont.)
Flow temperature control
Differential temperature:
The differential temperature may be
adjusted via coding address 05.
As delivered condition: 8K.
The boiler water temperature should
be higher than the currently required
flow temperature of the mixer circuit
by a minimum value, called the
differential temperature.
H
System with only one mixer circuit:
The set boiler water temperature
will be automatically held 8 K
above the set flow temperature.
H
System with a heating circuit
without mixer and with a mixer
circuit:
The set boiler water temperature
operates in accordance with a
special heating curve. The
differential temperature of 8 K
towards the set flow temperature is
set up at the factory.
A
Max. boiler water temperature
B
Slope = 1.8 boiler circuit A1
C
Slope = 1.2 mixer circuit M2
D
Boiler water temperature
(with differential temperature = 8 K)
E
Lower boiler water temperature
5862700GB
Boiler w
ater temperature or
flow temperature in °C
Outside temperature in °C
Содержание Vitotronic 200 KW2
Страница 22: ...22 Installation Installing the top part of the control unit 5862 700 GB 7 5 1 4 6 2 3 ...
Страница 23: ...23 Installation Opening the control unit 5862 700 GB 3 2 1 ...
Страница 104: ...104 Coding 5862 700 GB ...
Страница 106: ...106 Parts list Parts list cont 5862 700 GB 070 010 042 043 065 019 020 018 074 013 015 074 040 041 ...
Страница 108: ...108 Connection and wiring diagram Connection and wiring diagram 5862 700 GB F2 4A slow 250V F1 slow 6 3A 250V ...
Страница 118: ...118 5862 700 GB ...
Страница 119: ...119 5862 700 GB ...