100
Coding
Code 2
(cont.)
Coding in the delivered condition
Possible change
Mixer circuit
F1
:
0
Screed drying function
inactive
F1
:
1
to
F1
:
4
Screed drying function
adjustable in accordance
with four optional
temperature−time profiles
(see page 102)
Note
Observe the screed drying
supplier’s instructions.
Observe DIN 47252.
The report to be provided
by the heating contractor
must contain the following
heat−up details:
H
Heat−up data with
respective flow
temperatures
H
Max. flow temperature
achieved
H
Operating condition and
outside temperature
during handover.
The function continues
after power failure or after
the control unit has been
switched OFF.
The
Heating and DHW
program will be started,
after the screed−drying
function has been
completed or if the address
is manually set to 0.
5862700GB