18
Installation
External connection to plug X12
!
Please note
’Live’ contacts lead to short circuits or phase failure. The external
connections
must
be
zero volt
.
A
External start
(zero volt contact)
Rated voltage: 230 V~
Rated current: 6 A ~
Recommended
connecting
cable:
H05VVF3G 0.75 mm
2
External burner start (stage 1)
Connect the zero volt contact. If the
contact is closed, the first burner
stage is started, and the boiler water
temperature is regulated by the
control thermostat.
5862700GB
X12
A
1 2