19
Installation
Burner connection
Pressure−jet oil/gas burner
Connect the burner to DIN 4791.
The burner cables are included in the standard boiler delivery.
Max. current 4 (2) A.
A
To control unit
B
To burner
Burner without plug
Install the mating plug from
Viessmann or from the burner
manufacturer; connect the burner
cable.
Terminal codes
L1
Phase via high limit safety
cut−out to the burner
PE
Earthing conductor to burner
N
Neutral conductor to burner
T1,T2 Control chain
S3
Connection for burner fault
B4
Connection for hours run
meter
B
Signal pass direction:
Control unit
→
burner
Y
Signal pass direction:
Burner
→
control unit
Equipment codes
STB
High limit safety cut−out of
control unit
TR
Control thermostat
H1
Burner fault signal
BZ
Hours run meter
5862700GB
A
B
F
ault H1