17
Installation
Pump connection
Available pump connections
sÖ
Heating circuit pump A1 and M2
sA
Cylinder primary pump
sK
DHW circulation pump
Pumps 230 V~
Pumps 400 V~
A
Contactor
B
Three−phase pump
Rated current: 4 (2) A~
Recommended
connecting
cable:
H05VVF3G 0.75 mm
2
or
H05RNF3G 0.75 mm
2
For selecting the contactor:
Rated voltage: 230 V~
Rated current: 4 (2) A ~
Recommended
connecting
cable:
H05VVF3G 0.75 mm
2
or
H05RNF3G 0.75 mm
2
Variable speed pump
Connect at plug
aVG
in the control unit or in the KM BUS distributor.
5862700GB
M
1~
L
N
L1 L2 L3 N PE
M
3~
A
B