Coding
Code 1
(cont.)
Summary
Coding in the delivered condition
Possible change
System design
00 : 1
System version 1:
1 heating circuit without
mixerA1, without DHW
heating
00 : 2
System version 1:
1 heating circuit without
mixerA1,
with DHW heating
g
00 : 3
System version 2:
1 mixer circuit M2, without
DHW heating
00 : 4
System version 2:
1 mixer circuit M2,
with DHW heating
00 : 5
System version 3:
1 heating circuit without
mixerA1 and 1 mixer
circuitM2, without DHW
heating
00 : 6
System version 3:
1 heating circuit without
mixerA1,
1 mixer circuitM2,
with DHW heating
Burner type
02 : 0
Single stage
02 : 1
02 : 2
Two−stage
Modulating
Max. boiler temp.
06 : 85
Maximum limit of the
boiler water temperature
set to 85
º
C
06 : 20
to
06 : 130
Maximum limit of the
boiler water temperature
adjustable from 20 to
130
º
C
DHW priority A1
A2 : 2
Cylinder priority to
A2 : 0
Without cylinder priority
y
p
y
heating circuit pump
A2 : 1
A2 : 3
to
A2 : 15
No function
5862700GB
Содержание Vitotronic 200 KW2
Страница 22: ...22 Installation Installing the top part of the control unit 5862 700 GB 7 5 1 4 6 2 3 ...
Страница 23: ...23 Installation Opening the control unit 5862 700 GB 3 2 1 ...
Страница 104: ...104 Coding 5862 700 GB ...
Страница 106: ...106 Parts list Parts list cont 5862 700 GB 070 010 042 043 065 019 020 018 074 013 015 074 040 041 ...
Страница 108: ...108 Connection and wiring diagram Connection and wiring diagram 5862 700 GB F2 4A slow 250V F1 slow 6 3A 250V ...
Страница 118: ...118 5862 700 GB ...
Страница 119: ...119 5862 700 GB ...