28
Commissioning
Adjusting heating curves
(cont.)
Adjust the set room temperature
(for each heating circuit separately)
Standard room temperature:
Select the set day temperature with
the set value adjuster.
The value will be automatically
adopted after approx. 2s.
Reduced room temperature:
1.
Call up the set night temperature
with
E
.
2.
Change the value with
a
or
b
.
3.
Confirm the set value with
d
.
Examples
Adjustment of the standard room
temperature from 20
º
C to 26
º
C
Adjustment of the reduced room
temperature from 5
º
C to 14
º
C
A
Boiler water temperature or flow
temperature in
º
C
B
Outside temperature in
º
C
C
Set room temperature in
º
C
D
Heating circuit pump OFF
E
Heating circuit pump ON
Accordingly, the heating curve is
adjusted along the set room
temperature axis, which results in
modified start/shutdown
characteristics of the heating circuit
pumps, if the heating circuit pump
logic is activated.
5862700GB
D
E
D
E
Содержание Vitotronic 200 KW2
Страница 22: ...22 Installation Installing the top part of the control unit 5862 700 GB 7 5 1 4 6 2 3 ...
Страница 23: ...23 Installation Opening the control unit 5862 700 GB 3 2 1 ...
Страница 104: ...104 Coding 5862 700 GB ...
Страница 106: ...106 Parts list Parts list cont 5862 700 GB 070 010 042 043 065 019 020 018 074 013 015 074 040 041 ...
Страница 108: ...108 Connection and wiring diagram Connection and wiring diagram 5862 700 GB F2 4A slow 250V F1 slow 6 3A 250V ...
Страница 118: ...118 5862 700 GB ...
Страница 119: ...119 5862 700 GB ...