81
Coding
Code 1
(cont.)
Coding in the delivered condition
Possible change
Summer funct. A1
A5 : 5
With heating circuit pump
logic function
A5 : 0
Without heating circuit
pump logic function
Slope A1
d3 : 14
Do not adjust
Level A1
d4 : 0
Do not adjust
DHW priority M2
A2 : 2
Cylinder priority
A2 : 0
Without cylinder priority
y
p
y
applicable to heating
circuit pump and mixer
A2 : 1
Cylinder priority only
applicable to mixer
A2 : 3
to
A2 : 15
Modulating cylinder
priority
Summer funct. M2
A5 : 5
With heating circuit pump
logic function
A5 : 0
Without heating circuit
pump logic function
Min. supply temp. M2
C5: 20
Electronic minimum flow
temperature limit 20
º
C
C5: 1
to
C5 : 127
Minimum limit adjustable
from 1 to 127
º
C (only for
operation with standard
room temperature)
Max. supply. temp. M2
C6: 75
Electronic maximum limit
of the flow temperature
set to 75
º
C
C6: 1
to
C6 : 127
Maximum limit adjustable
from 1 to 127
º
C
Slope M2
d3 : 14
Do not adjust
Level M2
d4 : 0
Do not adjust
5862700GB
Содержание Vitotronic 200 KW2
Страница 22: ...22 Installation Installing the top part of the control unit 5862 700 GB 7 5 1 4 6 2 3 ...
Страница 23: ...23 Installation Opening the control unit 5862 700 GB 3 2 1 ...
Страница 104: ...104 Coding 5862 700 GB ...
Страница 106: ...106 Parts list Parts list cont 5862 700 GB 070 010 042 043 065 019 020 018 074 013 015 074 040 041 ...
Страница 108: ...108 Connection and wiring diagram Connection and wiring diagram 5862 700 GB F2 4A slow 250V F1 slow 6 3A 250V ...
Страница 118: ...118 5862 700 GB ...
Страница 119: ...119 5862 700 GB ...