85
Coding
Code 2
(cont.)
Coding in the delivered condition
Possible change
Boiler/burner
(cont.)
1F
:
0
With flue gas temperature
sensor:
The flue gas temperature
is not monitored
1F:
1
to
1F
:
500
Maintenance
will be displayed,
if the adjustable flue gas
temperature limit (from 1 to
500
º
C) has been exceeded
21
:
0
No burner maintenance
indication
21:
1
to
21
:
9
999
The number of hours run
before the burner should be
serviced is adjustable from 1 to
9
999h
23
:
0
No time interval for
burner maintenance
23:
1
to
23
:
24
Time interval adjustable from 1
to 24months
24
:
0
No
Maintenance
display
24
:
1
Maintenance
display (the
address is automatically set
and must be manually reset
after maintenance has been
carried out)
26
:
0
Burner fuel consumption
(stage 1):
No counting
26:
1
to
26
:
9
999
Enter 1 to 9999;
1 setting step
¢
0.1 litres or
gallons/h
28
:
0
No burner interval
ignition
28
:
1
The burner will be force−started
for 30s after 5h
29
:
0
Burner fuel consumption
(stage 2):
No counting
29
:
1
to
29
:
9
999
Enter 1 to 9999;
1 setting step
¢
0.1 litres or
gallons/h
32
:
70
With control module V:
Minimum set boiler
water temperature 70
º
C
for external burner
demand
32
:
0
to
32
:
127
Minimum set boiler water
temperature adjustable
from 0 to 127
º
C;
Note the adjustment of
thermostat
R
5862700GB
Содержание Vitotronic 200 KW2
Страница 22: ...22 Installation Installing the top part of the control unit 5862 700 GB 7 5 1 4 6 2 3 ...
Страница 23: ...23 Installation Opening the control unit 5862 700 GB 3 2 1 ...
Страница 104: ...104 Coding 5862 700 GB ...
Страница 106: ...106 Parts list Parts list cont 5862 700 GB 070 010 042 043 065 019 020 018 074 013 015 074 040 041 ...
Страница 108: ...108 Connection and wiring diagram Connection and wiring diagram 5862 700 GB F2 4A slow 250V F1 slow 6 3A 250V ...
Страница 118: ...118 5862 700 GB ...
Страница 119: ...119 5862 700 GB ...