Installation
Mains power supply
Regulations
Carry out the mains connection and all earthing measures (e.g. fault current
circuit) to IEC 364, the requirements of your local electricity supplier, VDE
regulations or all local and national regulations. The power supply to the
control unit should be protected by a fuse with a max. rating of 16 A.
Mains electrical isolator requirements
(if necessary)
For combustion equipment to DIN VDE 0116, the mains electrical isolator
fitted on site must comply with the requirements of DIN VDE 0116 Section 6
[or local regulations]. The mains electrical isolator must be installed outside
the installation area and must simultaneously isolate
all
non−earthed
conductors with at least 3 mm contact separation.
Replacing the mains connecting cable
3core cable selected from the following options:
H
H05VVF3G 0.75 mm
2
H
H05RNF3G 0.75 mm
2
A
Mains voltage 230 V~
B
Fuse (max. 16 A~)
C
Mains electrical isolator, 2−pole
(on site)
D
Junction box (on site)
1.
Check whether the cable to the
control unit is fitted with a fuse
with a max. rating of 16 A.
2.
Terminate the enclosed mains
connecting cable inside the
junction box (on site).
¨
Danger
Incorrect core allocations can
cause major damage to the
equipment.
Do not interchange cores L1
and N:
L1: brown
N:
blue
PE: green/yellow
3.
Insert plug
fÖ
into the control unit.
Colour coding to DIN IEC60757
BN
brown
BU
blue
GNYE green/yellow
5862700GB
D
L1
PE
N
A
B
C
Содержание Vitotronic 200 KW2
Страница 22: ...22 Installation Installing the top part of the control unit 5862 700 GB 7 5 1 4 6 2 3 ...
Страница 23: ...23 Installation Opening the control unit 5862 700 GB 3 2 1 ...
Страница 104: ...104 Coding 5862 700 GB ...
Страница 106: ...106 Parts list Parts list cont 5862 700 GB 070 010 042 043 065 019 020 018 074 013 015 074 040 041 ...
Страница 108: ...108 Connection and wiring diagram Connection and wiring diagram 5862 700 GB F2 4A slow 250V F1 slow 6 3A 250V ...
Страница 118: ...118 5862 700 GB ...
Страница 119: ...119 5862 700 GB ...