Components
Remote control
(cont.)
Version 2
A
To control unit
B
Socket (on site)
C
Vitotrol 1
D
Vitotrol 2
E
Further KM BUS users
H
If several remote control units and
additional KM BUS users are
connected, make the connections
via a socket (on−site) as shown in
the diagram.
H
The total length of all KM BUS
cables must be limited to 50 m.
5862700GB
145
A
max.
15 m
B
C
D
E
max. 15 m