103
Coding
Burner switching hysteresis
Switching hysteresis 4 K (04:0)
Heat demand−dependent switching hysteresis
ERB50 function (04:1)
Subject to heat demand, values between 6 and 12 K (Kelvin) result.
ERB80 function (04:2)
Subject to heat demand, values between 6 and 20 K (Kelvin) result.
The heat demand−dependent switching hysteresis, therefore, takes the boiler
load into account.
The switching hysteresis, i.e. the burner operating time, is varied subject to
current heat demand.
5862700GB
Burner
+2
ON
OFF
−2
lower
heat demand
average
heat demand
higher
heat demand
Time
set
lower
heat demand
average
heat demand
higher
heat demand
Time
Burner
ON
OFF
+9
−3
set
+3
lower
heat demand
average
heat demand
higher
heat demand
Time
Burner
ON
OFF
+17
−3
set
+3