63
"General"/Group 1
Select
"General"
for weather-compensated control
units (see page 62).
Select
"1"
for constant temperature control unit (see
page 62).
Coding
Coding in the delivered condition
Possible change
00:2
One heating circuit without mixer
A1 (heating circuit 1)
00:4
to
00:10
For system schemes, see the follow-
ing table:
Value, ad-
dress 00: ...
Description
2
One heating circuit without mixer A1 (heating circuit 1) (code is set automatically)
4
One heating circuit with mixer M2 (heating circuit 2)
6
One heating circuit without mixer A1 (heating circuit 1)
One heating circuit with mixer M2 (heating circuit 2)
(code is set automatically)
8
One heating circuit with mixer M2 (heating circuit 2)
One heating circuit with mixer M3 (heating circuit 3)
10
One heating circuit without mixer A1 (heating circuit 1)
Two heating circuits with mixer M2 (heating circuit 2) and M3 (heating circuit 3)
(code is set automatically)
Coding in the delivered condition
Possible change
11:≠9
No access to the coding addresses
for the combustion control parame-
ters
11:9
Access to the coding addresses for
the combustion control parameters
is open
25:0
Without outside temperature sen-
sor (for constant temperature con-
trol units)
25:1
With outside temperature sensor
(automatic recognition)
2A:0
Without wireless outside tempera-
ture sensor
2A:1
With wireless outside temperature
sensor (automatic recognition)
2A:2
Wireless outside temperature sensor
is not used
2d:0
Never adjust
32:0
Without AM1 extension
32:1
With AM1 extension (automatic rec-
ognition)
33:1
Function of A1 output at AM1 ex-
tension:
Heating circuit pump
33:0
DHW circulation pump
33:2
Circulation pump for cylinder heating
34:0
Function of output A2 at AM1 ex-
tension:
DHW circulation pump
34:1
Heating circuit pump
34:2
Circulation pump for cylinder heating
35:0
Without EA1 extension
35:1
With EA1 extension (automatic rec-
ognition)
36:0
Function of output
aBJ
at EA1 ex-
tension:
Fault message
36:1
Feed pump
36:2
DHW circulation pump
3A:0
Function of DE1 input at EA1 ex-
tension:
No function
3A:1
Heating program changeover
3A:2
External demand with set flow tem-
perature.
Codes
Coding level 2
(cont.)
5773 216 GB
Codes
Содержание B2TA
Страница 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...
Страница 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...
Страница 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...
Страница 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Страница 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Страница 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Страница 142: ...142 5773 216 GB ...
Страница 143: ...143 5773 216 GB ...