66
Coding in the delivered condition
Possible change
Control unit is fault manager (only
for weather-compensated control
units)
7b:1
With LON communication module:
Control unit transmits the time (on-
ly for weather-compensated con-
trol units)
7b:0
Does not transmit time
7F:1
Detached house (only for weather-
compensated control units)
7F:0
Apartment building
Holiday program and time program
for DHW heating can be set sepa-
rately
80:6
A fault message appears if a fault
is active for at least 30s
80:0
Immediate fault message
80:2
to
80:199
The minimum fault duration until a
fault message is issued is adjustable
from 10 to 995 s.
1 step
≙
5 s
81:1
Automatic summer/wintertime
changeover
81:0
Manual summer/wintertime change-
over
81:2
Use of the radio clock receiver (au-
tomatic recognition)
81:3
With LON communication module:
Control unit receives the time
82:0
Operation with natural gas
82:1
Operation with LPG (only adjustable
if coding address "11:9" has been
set)
86:...
Do not adjust
87:...
Do not adjust
88:0
Temperature displayed in °C (Cel-
sius)
88:1
Temperature displayed in °F (Fah-
renheit)
8A:175
Do not adjust
8F:0
Control in standard menu and in
extended menu is enabled.
Note
The respective code is only activa-
ted when you exit the service
menu (see page 75).
8F:1
Control in standard menu
and
in ex-
tended menu is locked.
Emissions test mode can be ena-
bled.
8F:2
Control in standard menu is ena-
bled, but locked in extended menu.
Emissions test mode can be ena-
bled.
90:128
Time constant for calculating the
adjusted outside temperature
21.3 h
90:1
to
90:199
Subject to the set value, the flow
temperature is adjusted quickly (low-
er values) or slowly (higher values)
when the outside temperature
changes.
1 step
≙
10 min
94:0
Without OpenTherm extension
94:1
With OpenTherm extension (auto-
matic recognition)
95:0
Without Vitocom 100, type GSM
communication interface
95:1
With Vitocom 100 communication in-
terface (automatic recognition)
97:0
With LON communication module:
Outside temperature of the sensor
connected to the control unit is uti-
lised internally (only for weather-
compensated control units)
97:1
Control unit receives outside tem-
perature
97:2
Control unit transmits outside tem-
perature to the Vitotronic 200-H
Codes
Coding level 2
(cont.)
5773 216 GB
Codes
Содержание B2TA
Страница 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...
Страница 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...
Страница 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...
Страница 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Страница 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Страница 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Страница 142: ...142 5773 216 GB ...
Страница 143: ...143 5773 216 GB ...