60
Coding in the delivered condition
Possible change
Min. flow temperature heating circuit
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only in operation
with standard room temperature;
only for weather-compensated
control units)
C5:1
to
C5:127
Minimum limit adjustable from 1 to
127 °C (limited by boiler-specific pa-
rameters)
Max. flow temperature heating circuit
C6:74
Electronic maximum flow tempera-
ture limit 74 °C (only for weather-
compensated control units)
C6:10
to
C6:127
Maximum limit adjustable from 10 to
127 °C (limited by boiler-specific pa-
rameters)
Heating program changeover
d5:0
With external heating program
changeover (observe setting for
coding addresses "3A", "3b" and
"3C" in the
"General"
group).
Operating program switches to
"Constant central heating with re-
duced room temperature" or
"Standby mode" (subject to the
settings of the set reduced room
temperature) (only for weather-
compensated control units).
d5:1
Heating program switches to "Con-
stant operation with standard room
temperature".
Ext. heating program changeover to heating circuit
d8:0
With EA1 extension:
No operating program changeover.
d8:1
Operating program changeover via
input DE1.
d8:2
Operating program changeover via
input DE2.
d8:3
Operating program changeover via
input DE3.
Max. pump speed in standard mode
E6:...
Only for heating systems without a
heating circuit with mixer:
Maximum speed of the internal
speed-controlled heating circuit
pump in % of the max. speed in
standard mode. Value is specified
by boiler-specific parameters (only
for weather-compensated control
units).
E6:0
to
E6:100
Maximum speed adjustable from 0
to 100 %
Min. pump speed
E7:30
Only for heating systems without a
heating circuit with mixer:
Minimum speed of the internal
speed-controlled heating circuit
pump:
30 % of the max. speed (only for
weather-compensated control
units)
E7:0
to
E7:100
Minimum speed adjustable from 0 to
100 % of the maximum speed
Screed drying
F1:0
Screed drying disabled (only for
weather-compensated control
units).
F1:1
to
F1:6
Only for heating circuit with mixer:
Screed drying adjustable, with
choice of 6 temperature/time profiles
(see page 128)
F1:15
Constant flow temperature 20 °C
Codes
Coding level 1
(cont.)
5773 216 GB
Codes
Содержание B2TA
Страница 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...
Страница 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...
Страница 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...
Страница 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Страница 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Страница 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Страница 142: ...142 5773 216 GB ...
Страница 143: ...143 5773 216 GB ...