58
Coding
Coding in the delivered condition
Possible change
Enable DHW circulation pump
73:0
DHW circulation pump: "ON" ac-
cording to time program (only for
weather-compensated control
units)
73:1
to
73:6
During time program
"ON" from once per hour for 5 min to
"ON" 6 times per hour for 5 min
73:7
Constantly "ON"
"Heating circuit ..."/Group 5
Select
"Heating circuit ..."
for weather-compensated
control unit (see page 55).
Select
"5"
for constant temperature control unit (see
page 55).
Coding
Coding in the delivered condition
Possible change
Economy function outside temperature
A5:5
With heating circuit pump logic
function (economy control): Heat-
ing circuit pump is "OFF" when the
outside temperature (OT) is 1 K
higher than the set room tempera-
ture (RT
set
)
OT
>
RT
set
+ 1 K (only for weather-
compensated control units)
A5:0
Without heating circuit pump logic
function
A5:1
to
A5:15
With heating circuit pump logic func-
tion: Heating circuit pump "OFF",
see following table
Parameter address A5:...
With heating circuit pump logic function: Heating circuit pump "OFF"
1
OT
>
RT
set
+ 5 K
2
OT
>
RT
set
+ 4 K
3
OT
>
RT
set
+ 3 K
4
OT
>
RT
set
+ 2 K
5
OT
>
RT
set
+ 1 K
6
OT
>
RT
set
7
to
OT
>
RT
set
–
1 K
15
OT
>
RT
set
–
9 K
Coding in the delivered condition
Possible change
Extended economy function adjusted outside temperature
A6:36
Extended economy control
disa-
bled
(only for weather-compensa-
ted control units)
A6:5
to
A6:35
Extended economy mode enabled;
i.e. at a variably adjustable value be-
tween 5 and 35 °C, plus 1 °C, the
burner and heating circuit pump stop
and the mixer closes. The basis for
this is the adjusted outside tempera-
ture. The adjusted outside tempera-
ture is based on the actual outside
temperature and a time constant,
which takes into account the cooling
down of an average building.
Codes
Coding level 1
(cont.)
5773 216 GB
Codes
Содержание B2TA
Страница 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...
Страница 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...
Страница 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...
Страница 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Страница 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Страница 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Страница 142: ...142 5773 216 GB ...
Страница 143: ...143 5773 216 GB ...