Example using the settings in the delivered condition
10
0
20
30
30
40
50
60
6
7
8
9
Boiler
water
temperature/
set flow temperature
in
°C
Time
A
B
C
D
Fig. 92
A
Start of operation with standard room temperature
B
Set boiler water or flow temperature in accordance
with the selected heating curve
C
Set boiler water or flow temperature in accordance
with coding address "FA":
50 °C + 20 % = 60 °C
D
Duration of operation with raised set boiler water
or flow temperature in accordance with coding
address "Fb":
60 min
Allocating heating circuits to the remote control
The heating circuit allocation must be configured when
commissioning the Vitotrol.
Heating circuit
Vitotrol configuration
200A/200 RF
300A/300 RF
The remote control affects the heating circuit without mixer A1
H 1
HC 1
The remote control affects the heating circuit with mixer M2
H 2
HC 2
The remote control affects the heating circuit with mixer M3
H 3
HC 3
Note
One heating circuit can be assigned to the Vitotrol
200A/200 RF.
Up to three heating circuits can be assigned to the
Vitotrol 300A/300 RF.
Up to 2 remote controls may be connected to the con-
trol unit.
If the heating circuit allocation is later cancelled, reset
coding address A0 for this heating circuit to 0 (fault
message bC, bd, bE).
Function description
Control functions
(cont.)
5773 216 GB
Functions
Содержание B2TA
Страница 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...
Страница 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...
Страница 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...
Страница 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Страница 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Страница 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Страница 142: ...142 5773 216 GB ...
Страница 143: ...143 5773 216 GB ...