38
C
B
A
Fig. 30
1.
Check at the siphon that the condensate can drain
freely.
2.
Remove retaining clip
A
.
3.
Pull filler pipe
B
upwards.
4.
Remove trap
C
downwards.
5.
Remove the condensate hose from trap
C
.
6.
Clean the siphon.
7.
Fill siphon with water and reassemble with retaining
clip
A
.
8.
Check that the condensate pipe is connected cor-
rectly to the siphon and heat exchanger.
Note
Route the drain hose without any bends and with a
constant fall.
Commissioning, inspection, maintenance
Checking the condensate drain and cleaning the…
(cont.)
5773 216 GB