65
Coding in the delivered condition
Possible change
3C:6
Brief operation of DHW circulation
pump (pushbutton function).
Adjustment of DHW circulation
pump runtime: Coding address "3d"
in this group
3d:5
Runtime of DHW circulation pump
during brief operation: 5 min
3d:1
to
3d:60
DHW circulation pump runtime ad-
justable from 1 to 60 min
3E:0
Internal circulation pump stays in
control mode at signal "External
blocking"
3E:1
Internal circulation pump stops at
signal "External blocking"
3E:2
Internal circulation pump starts at
signal "External blocking"
3F:0
Internal circulation pump stays in
control mode at signal "External
demand"
3F:1
Internal circulation pump stops at
signal "External demand"
3F:2
Internal circulation pump starts at
signal "External demand"
51:0
The internal circulation pump al-
ways starts when there is a heat
demand.
51:1
System with low loss header:
The internal circulation pump only
starts upon heat demand if the burn-
er is running.
Circulation pump stops on expiry of
the run-on time.
51:2
System with heating water buffer
cylinder:
The internal circulation pump only
starts upon heat demand if the burn-
er is running.
Circulation pump stops on expiry of
the run-on time.
52:0
Without flow temperature sensor
for low loss header
52:1
With flow temperature sensor for low
loss header (automatic recognition)
53:1
Function of terminal
sÖ
/
sK
of inter-
nal H1/H2 extension:
DHW circulation pump
53:0
Central fault
53:2
External heating circuit pump (heat-
ing circuit 1)
53:3
Do not adjust
54:0
Never adjust
6E:50
No display correction for outside
temperature.
6E:0
to
6E:49
Display correction
–
5 K
to
Display correction
–
0.1 K
6E:51
to
6E:99
Display corr0.1 K
to
Display corr4.9 K
76:0
Without LON communication mod-
ule (only for weather-compensated
control units)
76:1
With LON communication module
(automatic recognition)
77:1
LON subscriber number (only for
weather-compensated control
units)
77:2
to
77:99
LON subscriber number adjustable
from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
79:1
With LON communication module:
79:0
Control unit is not fault manager
Codes
Coding level 2
(cont.)
5773 216 GB
Codes
Содержание B2TA
Страница 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...
Страница 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...
Страница 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...
Страница 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Страница 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Страница 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Страница 142: ...142 5773 216 GB ...
Страница 143: ...143 5773 216 GB ...