56
Coding
Coding in the delivered condition
Possible change
System design
00:2
One heating circuit without mixer
A1 (heating circuit 1)
00:4
to
00:10
For system schemes, see the follow-
ing table:
Value, ad-
dress 00: ...
Description
2
One heating circuit without mixer A1 (heating circuit 1) (code is set automatically)
4
One heating circuit with mixer M2 (heating circuit 2)
6
One heating circuit without mixer A1 (heating circuit 1)
One heating circuit with mixer M2 (heating circuit 2)
(code is set automatically)
8
One heating circuit with mixer M2 (heating circuit 2)
One heating circuit with mixer M3 (heating circuit 3)
10
One heating circuit without mixer A1 (heating circuit 1)
Two heating circuits with mixer M2 (heating circuit 2) and M3 (heating circuit 3)
(code is set automatically)
Coding in the delivered condition
Possible change
Internal circulation pump function
51:0
The internal circulation pump al-
ways starts when there is a heat
demand.
51:1
System with low loss header:
The internal circulation pump only
starts upon heat demand if the burn-
er is running.
Circulation pump stops on expiry of
the run-on time.
51:2
System with heating water buffer
cylinder:
The internal circulation pump only
starts upon heat demand if the burn-
er is running.
Circulation pump stops on expiry of
the run-on time.
Subscriber no.
77:1
LON subscriber number (only for
weather-compensated control
units)
77:2
to
77:99
LON subscriber number adjustable
from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Detached house/apartment building
7F:1
Detached house (only for weather-
compensated control units)
7F:0
Apartment building
Holiday program and time program
for DHW heating can be set sepa-
rately
Codes
Coding level 1
(cont.)
5773 216 GB
Codes
Содержание B2TA
Страница 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...
Страница 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...
Страница 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...
Страница 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Страница 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Страница 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Страница 142: ...142 5773 216 GB ...