64
Coding in the delivered condition
Possible change
Set value setting: Coding address
"9b" in this group.
Internal circulation pump function:
Coding address "3F" in this group.
3A:3
External blocking.
Internal circulation pump function:
Coding address "3E" in this group.
3A:4
External blocking with fault message
input.
Internal circulation pump function:
Coding address "3E" in this group.
3A:5
Fault message input
3A:6
Brief operation of DHW circulation
pump (pushbutton function).
Adjustment of DHW circulation
pump runtime: Coding address "3d"
in this group.
3b:0
Function of DE2 input at EA1 ex-
tension:
No function
3b:1
Heating program changeover
3b:2
External demand with set flow tem-
perature.
Set value setting: Coding address
"9b" in this group.
Internal circulation pump function:
Coding address "3F" in this group.
3b:3
Function of DE2 input: External
blocking.
Internal circulation pump function:
Coding address "3E" in this group.
3b:4
Function of DE2 input: External
blocking with fault message input
Internal circulation pump function:
Coding address 3E
3b:5
Function of DE2 input: Fault mes-
sage input
3b:6
Function of DE2 input: Brief opera-
tion of DHW circulation pump (push-
button function).
Adjustment of DHW circulation
pump runtime: Coding address 3d
3C:0
Function of DE3 input at EA1 ex-
tension:
No function
3C:1
Heating program changeover
3C:2
External demand with set flow tem-
perature.
Set value setting: Coding address
"9b" in this group.
Internal circulation pump function:
Coding address "3F" in this group.
3C:3
External blocking.
Internal circulation pump function:
Coding address "3E" in this group.
3C:4
External blocking with fault message
input
Internal circulation pump function:
Coding address "3E" in this group.
3C:5
Fault message input
Codes
Coding level 2
(cont.)
5773 216 GB
Codes
Содержание B2TA
Страница 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...
Страница 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...
Страница 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...
Страница 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Страница 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Страница 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Страница 142: ...142 5773 216 GB ...
Страница 143: ...143 5773 216 GB ...