Figure 28:
System Interface Circuit Card Connections
J5
CAN
TB2
TP3 (+) and TP4 (-)
System Load
Shunt Monitoring
TP1 (+) and TP2 (-)
System Voltage
Monitoring
TB1-1: Battery Tray FA
TB1-2: External Battery FA
TB1-3: External System FA
TB1-4: External Battery Monitoring (-)
TB1-5: External Battery Monitoring (+)
1
1A 2A 3A
1B 2B 3B
5
RS485 Connection
TB2 1A: RS485+
TB2 2A: RS485-
RS232 Connection
TB2 1B: CGND
TB2 2B: TXD232
TB2 3B:RXD232
J1
J2
J3
J4
J8
TB2
TB1
TP1 TP2 TP3 TP4
J10
J5
TB1
Wire Size Capacity: 22-12 AWG.
Recommended Torque: 3.0 in-lbs.
FA Signals: Battery applied to the terminal
turns in an alarm.
J1, J2, J3, J4
Distribution Panels FA Inputs
J8
Selects to power Controller
from “Battery Power” or not.
Shorting Jumper
No
Battery
Pwr
Battery
Pwr
External Internal
J8
J10
1
2
3
7
8
9
3 2 1
J10
Battery Monitoring External / Internal
(see TB1-4 and TB1-5 for
external monitoring points)
Shorting Jumper
CAN termination plug
must be installed.
System
Interface
Card