Programmable Relay Outputs
The EIB provides five (5) programmable alarm relays with dry Form-C contacts. Connect up to five (5) relay
outputs to the EIB. Refer to
Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for programming
information.
Relay Ratings: Refer to the following.
a)
Steady State: 0.5 A @ 60V DC; 1.0 A @ 30V DC.
b)
Peak: 3 A @ 30V DC.
The relays may be preprogrammed for specific functions. Refer to the configuration drawing (C-drawing)
supplied with your system for your system’s specific configuration.
Temperature Probes
Temperature probes can be connected to the optional EIB (Controller Extended Interface Board) mounted
inside the distribution cabinet. Refer to “Temperature Probes” on page 72.