Ethernet Connection through the Power System
The Ethernet cable can be routed from the notch on the left side of the bracket. It goes through the lances on
the chassis, then goes up to be bundled with the harness and all other customer alarm and signal cables.
The existing cable ties can also be used to secure the Ethernet cable as it goes up to the top panel.
Figure 34:
Network Connection through Power System
Bracket
notch
Lance
* Removed some parts
for illustrative purposes.
Cable
ties
Ethernet wire
coming out from one of
the rectangular openings
on top of cabinet panel