Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
128
Figure 78:
ACU+ Local Indicators and Navigation Keys
Procedure
NOTE!
The initialization routine takes several minutes. During that time various alarm indicators may
illuminate on the ACU+ front panel and an audible alarm may sound. Disregard all alarms. An audible
alarm can be silenced at any time by momentarily depressing the
ENT
key on the ACU+ Controller.
1.
After the ACU+ is powered on, the display alternates between the “logo” screen and a screen displaying
“Advanced Control Unit Plus Version ***** Starting….
2.
Next, the language screen appears. Press the up or down arrow key to select the desired language.
Press the ENT key to confirm the selection. If no key is pressed within 10 seconds, the ACU+ selects
the displayed language automatically.
3.
As initialization continues, the Main screen is displayed, but with zero volts. Initialization is not complete.
4.
When initialization is complete, the Main screen displays voltage and current normally, and no alarms are
active.
Status
Indicator
(Green)
Minor Alarm
Indicator (Yellow)
Critical or Major
Alarm Indicator
(Red)
ESC
ENT
Menu Navigation Keys
USB
Port
Ethernet
Port