Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
111
Figure 66:
List BH: Battery Disconnect Distribution Panel, (4) TPH Fuse Battery Disconnect Positions (with
Shunts) (without Return Busbar)
+24VDC Battery
Connections
BATTERY CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
or order additional
hardware)
Observe proper polarity
when making battery
connections.
WARNING!
Maximum Lug Width: 1.75 inches.
Maximum fuse size is 400A.
Содержание NetSure 710 Series