Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
51
Table 3:
Optional SM-DU+ Switch Settings
DIP Switch SW1
Reserved HW
/SW
Shunt
Voltage
Shunt
Current
Description of Status
1
2
3
4
5
6
7
8
NA
OFF
NA
Shunt parameter is set through DIP switch.
ON
Shunt parameter is set through software (note 1).
NA
OFF OFF
NA
Shunt Voltage: 25mV (note 1)
OFF ON
Shunt Voltage: 50mV
ON OFF
Shunt Voltage: 60mV
ON ON
Shunt Voltage: 75mV
NA
OFF OFF OFF
Shunt Current: 500A (note 1)
OFF OFF
ON
Shunt Current: 100A
OFF ON
OFF
Shunt Current: 200A
OFF ON
ON
Shunt Current: 300A
ON OFF OFF
Shunt Current: 400A
ON OFF
ON
Shunt Current: 1000A
ON
ON
OFF
Shunt Current: 1500A
ON
ON
ON
Shunt Current: 2000A
DIP Switch SW2
Reserved
Communications
Address
Baud
Rate
Description of Status
1
2
3
4
5
6
7
8
NA
OFF OFF OFF
NA
Address 1# (Setting for SM-DU+ in this system)
OFF OFF ON
Address 2#
OFF ON OFF
Address 3#
OFF ON
ON
Address 4#
ON OFF OFF
Address 5#
ON OFF ON
Address 6#
ON ON OFF
Address 7#
ON ON
ON
Address 8#
NA
OFF
19200 (note 1)
ON
9600
Note 1: Setting for this system.