NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
18
Mounting System Components in an Equipment Rack
NOTE!
If the power system was ordered in a relay rack, these procedures have been performed at the
factory.
This power system is designed to mount in a standard 23” relay rack having 1” or 1-3/4” multiple drillings. Refer
to System Application Guide SAG581127000 for overall dimensions and a list of available relay racks.
Mounting the Distribution Cabinet with Module Mounting Assembly
NOTE!
The distribution cabinet is factory connected to the module mounting assembly. The
distribution cabinet with module mounting assembly is mounted as a complete assembly.
The distribution cabinet with module mounting assembly must be the top-most component in the rack.
Perform the following steps to mount the distribution cabinet with module mounting assembly.
DANGER!
The relay rack must be securely anchored to the floor before the distribution cabinet with
module mounting assembly is installed.
DANGER!
The distribution cabinet with module mounting assembly is heavy. Use a hoist, battery lift, or
other appropriate lifting device to raise and support the assembly during the installation. Take
appropriate precautions to avoid injury.
Procedure
1.
Remove the distribution cabinet with module mounting assembly from its shipping brackets. Position
the assembly in the equipment rack. Note that part of the AC wireways will have to be temporarily
removed from the distribution cabinet to access the mounting hardware.
NOTE!
Install the ground washers so the teeth dig into the paint on the mounting angles. Torque all
screws to 65 in-lbs.
2.
Mount the distribution cabinet to the relay rack using the following hardware. Refer to
a)
1-Row Cabinet: Install (8) 12-24 x 3/4" hex head thread-forming screws (P/N 218710600) and (8)
No. 12 ground washers (P/N 215640600).
b)
2-Row Cabinet: Install (10) 12-24 x 3/4" hex head thread-forming screws (P/N 218710600) and (10)
No. 12 ground washers (P/N 215640600).
c)
3-Row Cabinet: Install (12) 12-24 x 3/4" hex head thread-forming screws (P/N 218710600) and (12)
No. 12 ground washers (P/N 215640600).
d)
4-Row Cabinet: Install (16) 12-24 x 3/4" hex head thread-forming screws (P/N 218710600) and (16)
No. 12 ground washers (P/N 215640600).
3.
Mount the module mounting assembly to the relay rack using hardware as shown