Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
69
System Interface Circuit Card
The System Interface Circuit Card provides connections for the following. Refer to
•
Battery Tray FA Signal: This input is used to provide a battery tray fuse alarm (FA) on the controller due
to a tripped battery disconnect breaker on a battery tray in the power system rack. Application of
system voltage to pin TB1-1 activates this alarm. The lead should be protected at the source with an in-
line fusible resistor. The source should be originated from the system side of the disconnect device, not
the battery side. If used with List 93 battery tray option this connection is applied in the factory.
•
External Battery FA Signal: This input is used to provide an external battery fuse alarm (FA) on the
controller due to a tripped battery disconnect device (fuse, breaker or contactor) external to the power
system rack. Application of system voltage to pin TB1-2 activates this alarm. The lead should be
protected at the source with an in-line fusible resistor. The source should be originated from the system
side of the disconnect device, not the battery side.
•
External System FA Signal: This input is used to provide an external system fuse alarm (FA) on the
controller due to a tripped distribution device (fuse or breaker) on the system output external to the
power system distribution cabinet. Application of system voltage to pin TB1-3 activates this alarm. The
lead should be protected at the source with an in-line fusible resistor. This input is not to be used for
any voltage bus (such as converter output) other than the system bus.
•
External Battery Monitoring: If the jumper J10 is set to External (see
), connect TB1-4 and
TB1-5 to the desired battery voltage sensing point. Observe proper polarity per the
. The hot
sense lead should be protected at the source with an in-line fuse or fusible resistor.
•
RS-485 (used for communication with SM modules)
(Also used when an NCU configuration is furnished that enables NCU capability to receive status
information sent from Fiamm SoNick [Sodium Nickel] batteries. Connect leads from the Fiamm SoNick
batteries to the RS-485 terminals. See
. Refer to the battery manufacturer documentation
and the NCU controller manual UM1M830BNA for details.)
•
RS-232 (used for communication with a DPU)
•
Bay Voltage Monitoring Test Points: Provide system bus voltage measurement for an external meter.
The leads are protected against fault with 10kohm series resistors in each lead.
•
Bay Load Shunt Monitoring Test Points: Provide for measurement of the system load shunt in the bay.
See below for shunt ratings. The leads are protected against fault with 10kohm series resistors in each
lead.
List 21, 1-Row Distribution Cabinet: 800A / 25mV (32A per mV)
List 22, 2-Row Distribution Cabinet: 2000A / 25mV (80A per mV)
List 23, 3-Row Distribution Cabinet: 2500A / 25mV (100A per mV)
List 24, 4-Row Distribution Cabinet: 2500A / 25mV (100A per mV)