NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
109
Figure 62:
List BC: Battery Disconnect Distribution Panel (with Return Busbar) and List BD: Battery
Disconnect Distribution Panel (without Return Busbar), (4) GJ/218 Circuit Breaker Battery
Disconnect Positions
Figure 63:
List BE: Battery Disconnect Distribution Panel, (2) TPH Fuse Battery Disconnect Position (without
Shunts) (without Return Busbar)
+24VDC Battery
Connections
Battery Return
Connections
BATTERY AND BATTERY RETURN CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
1.375 inches.
Return Busbar
(not included
with List BD)
Observe proper polarity
when making battery
connections.
WARNING!
For an 800A circuit breaker,
load must not exceed 600A.
+24VDC Battery
Connections
BATTERY CONNECTIONS
3/8-16 Captive Nuts on 1” Centers Maximum Lug Width: 1.88 inches.
(Customer must supply
or order additional
hardware)
Observe proper polarity
when making battery
connections.