Supplementary installation, operating and maintenance instructions  English 

Explosion-proof three-phase asynchronous motors with squirrel-cage rotor for high voltage 

 
 

 
815001 Edition 09.2020                                                                                                                                                                                                                                                                                                                                                                                                         
 

10 

Shaft end upwards: 

For designs with the shaft at the top, the operator must prevent foreign bodies and water from falling vertically 
into the shaft. With the shaft end upwards, ingress of water or liquid along the shaft must also be prevented. 
When installing surface-cooled motors, it must also be ensured that the condensation water drain  holes are 
located at the lowest point. If the condensation water drain holes are sealed, sealant must be applied to the 
screws when they are replaced after draining the condensation water. In the case of open condensation water 
holes, direct exposure to water jets or splash water must be avoided.  Careful installation of the motors on a 
completely level surface is essential to avoid distortion when tightening them. Precise alignment of any ma-
chines to be connected must be ensured. If possible, flexible couplings should be used. 
 

1.10 General information on operation from the frequency inverter 

Operation of explosion-proof three-phase motors from the frequency inverter is only permitted if the motors 
are manufactured, tested, approved and separately marked for this type of operation. The separate manufac-
turer’s instructions must be observed.  
For the ignition protection type increased safety “eb” and motors for use in zone 21, separate EU (EC) Type 
Examination Certificates are required in which operation with the inverter is explicitly approved and in which 
the conditions to be observed and parameter settings of the system motor, inverter and protective device are 
specified.   
In ignition protection type “ec”, motors supplied with power by converters with variable frequency and/or volt-
age must also be tested with the specified converter or a converter that is comparable in terms of output volt-
age and current. Alternatively, the temperature class can be determined by calculation. The necessary pa-
rameters and conditions can be found on the rating plate or in the motor documentation. 
 

To avoid impermissible temperatures, the motors are always equipped with thermal winding protec-
tion, which must be checked with a suitable device. The motors must not be operated as group 
drives. 

 
For installation and commissioning of the frequency inverter, the manufacturer’s instructions and operating 
manual must be observed. 
 

Operation from the frequency inverter for use in zone 2, 22 (Ex II 3G, Ex II 3D) 

Operation with the frequency inverter is only permitted within the operating points specified on the rating 
plate. Exceeding the rated current for the machine by up to 1.5 times that rated current is permissible for a 
maximum of 1 minute within a period of 10 minutes.

 

The specified maximum speed or frequency must never 

be exceeded. By selecting the appropriate inverter and/or using filters, it must be ensured that the maximum 
permissible pulse voltage at the motor terminals is not exceeded.  
 
It must be ensured that the operating voltage applied to the motor terminals always corresponds to the infor-
mation on the rating plate (note voltage drop across filter!). The thermal winding protection must be checked 
either by a separate trigger device or by the inverter. 
 

Operation from the frequency inverter for use in zone 1, 21 (Ex II 2G, Ex II 2D) 

 

Motors for use in zone 1 or 21 must always be certified by an authorised body for operation with a frequency 
inverter. Limit values specified on the rating plate and on the EC Type Examination Certificate must be 
strictly observed. In particular, this also means monitoring the continuous current as a function of frequency. 
Only frequency inverters that meet the requirements specified on the EU (EC) Type Examination Certificate 
may be used.

 

Assessment of the integrated thermal winding protection must be carried out using a trigger 

unit with the Ex-marking II (2) G which complies with the requirements of Directive 2014/34/EU. The speci-
fied maximum speed or frequency must never be exceeded. It must be ensured that the operating voltage 
applied to the motor terminals always corresponds to the information on the rating plate (note voltage drop 
across filter!). If the terminal voltage at the motor is lower than the rated voltage specified on the rating plate 
due to voltage drops across the frequency inverter, the cables and any chokes or filters, the base frequency 
must be set to a lower value corresponding to a linear voltage/frequency assignment. This results in a 
smaller speed control range.  

 
1.11 Electromagnetic compatibility

 

When operating the motors from the frequency inverter, interference emissions can occur depending on the 
inverter type. Exceeding the limit values according to IEC/EN 61000-6-3 must be avoided for the drive sys-
tem consisting of motor and inverter. The EMC instructions of the inverter manufacturer must always be ob-
served. On machines with built-in PTC thermistors or other sensors, inverter-induced interference voltages 
can occur. 
 
 

Содержание W52R 355 Series

Страница 1: ...g and maintenance instructions Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage Ignition protection types Increased safety eb and ec Protection by enclosure t...

Страница 2: ...ge First edition 09 2015 11 2015 Annex 2 Update of EU Declaration of Conformity 01 2016 Change of section 5 7 to 5 8 Section 5 7 entry parts new Annex 4 new Change in the wording for the heating ca bl...

Страница 3: ...3 Risk assessment with regard to possible sparking in Ex eb IIC 3 Information about ignition protection type increased safety ec 3 1 Protective principle labelling 3 2 Risk assessment with regard to...

Страница 4: ...make changes to the product the technical data or the assembly operating and maintenance instructions without prior notice Designs technical data and illustra tions are only ever binding with written...

Страница 5: ...ng to IEC EN 60034 5 for motors used in zones 1 2 and 22 is a minimum of IP 55 For use in zone 21 the motors are designed to meet IP 65 as a minimum Only electrical machines with the approved type of...

Страница 6: ...erved 1 6 Transport and storage Any damage detected on delivery must be reported to the transport company immediately if necessary commissioning must be prevented Transport eyes attachment points are...

Страница 7: ...ain the temperature class and the permissible operating temperature The motor must not be enclosed Compare current type mains voltage and frequency Pay attention to the circuitry Observe rated current...

Страница 8: ...ions When inserting the supply cables into the terminal box make sure that the cables have strain relief The in side of the terminal boxes must be kept clean The seals must be undamaged and correctly...

Страница 9: ...eration If there are changes compared to normal operation e g increased tempera tures noises and vibrations the machine must be switched off in case of doubt The cause must be determined and the manuf...

Страница 10: ...ating manual must be observed Operation from the frequency inverter for use in zone 2 22 Ex II 3G Ex II 3D Operation with the frequency inverter is only permitted within the operating points specified...

Страница 11: ...ts are stated on the rating plate or on the EC Type Examination Certificate If the certificate number ends in an X special conditions on the EC Type Examination Certificate must be observed Electrical...

Страница 12: ...gap with squirrel cage rotors A risk assessment has been carried out by the manufacturer regarding possible sparking in the air gap of squirrel cage rotors If the sum of the factors is greater than 6...

Страница 13: ...tures of surfaces on which dust may be deposited or which may come into contact with a cloud of dust are kept below the temperatures specified in this standard All parts with electrical sparks or temp...

Страница 14: ...ox optional star point box The stator housing with feet is made of grey cast iron the bearing plates and terminal box are made of grey cast iron For high voltage motors a welded steel construction is...

Страница 15: ...connections must then be assembled with locking nuts taking into account the thickness of the plate The diameter of these through holes must be selected in accordance with DIN EN 50262 5 8 Standstill...

Страница 16: ...layers of dust lead to a temperature increase on the surface of the motor Dust deposits on motors and even their complete filling with dust must there fore be avoided as far as possible by appropriate...

Страница 17: ...t therefore be strictly observed by taking the following steps among others Limiting the total paint or resin layer thickness according to the explosion group to IIA IIB Total coating thickness 2 mm I...

Страница 18: ...ts list may be used this applies in particular to seals and connecting parts The following information is required when ordering spare parts Spare part designation Motor type Motor number 12 Disposal...

Страница 19: ...allation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 19 13 Terminal box construction...

Страница 20: ...5 4 1 5 5 1 5 6 1 5 7 1 5 8 1 5 9 1 5 10 1 5 13 1 5 15 1 6 1 1 6 5 1 7 2 1 7 4 1 Die Inbetriebnahme der unvollst ndigen Maschine ist solange untersagt bis die Konformit t der Maschine in welche die un...

Страница 21: ...Supplementary installation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 21 Annex 2...

Страница 22: ...Supplementary installation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 22...

Страница 23: ...tion of the flange is determined by the motor manufacturer Before putting the motor into operation the free volume of the motor enclosure must be purged with inert gas if necessary after ignition risk...

Страница 24: ...d on the equipment rating plate or terminal box Alternatively the number and position of the entry threads are indicated on the dimension drawing of the mo tor Unless otherwise ordered cable glands fr...

Страница 25: ...instead be approved according to IECEx or if selected by the plant operator they must be approved according to IECEx The motors are labelled as IECEx compliant For IECEx approved motors references to...