Supplementary installation, operating and maintenance instructions  English 

Explosion-proof three-phase asynchronous motors with squirrel-cage rotor for high voltage 

 
 

 
815001 Edition 09.2020                                                                                                                                                                                                                                                                                                                                                                                                         
 

avoid them. They must be authorised by the person responsible for the safety of the installation to carry out 
the necessary work and activities.

 

Before starting work, the following 5 safety rules must always be applied:

 

 

Disconnect  

 

Secure to prevent restarting  

 

Ensure absence of voltage  

 

Ground and short circuit  

 

Cover or cordon off adjacent live parts 

 
Auxiliary circuits (e.g. standstill heating) must also be disconnected.  
Exceeding the limit values of area A in IEC/EN 60034-1/ DIN VDE 0530 -1 

– voltage ±5%, frequency ±2%, 

waveform, symmetry 

– leads to increased heating. Observe the information on the rating plate and the wiring 

diagram in the terminal box. The connection must be made in such a way that a permanently safe electrical 
connection is maintained. Only approved cable end fittings must be used. Safe equipotential bonding must 
be established and ensured.  
Air gaps between bare, live parts and to earth must not fall below the following values: 

 

  36 mm for U

N

 

≤ 3.2 kV,  

 

  60 mm for U

N

 

≤ 6.3 kV  

The working voltage may exceed the specified voltage level by 10%. 
There must be no foreign bodies, dirt or moisture in the terminal box.  
For a test run without output elements, the feather key must be secured.  
High-voltage machines with accessories must be checked for proper function before commissioning.  
 

Proper installation (e.g. spatial separation of signal lines and power  

cables, shielded 

lines and cables, etc.) is the responsibility of the system 
             operator. 
 

Unventilated motors without integral fans are cooled by free convection with cooling fins on the motor hous-
ing. Adequate safety to prevent inadmissible heating is ensured by power reduction/winding adjustment and 
proven by means of type testing/submission. Free convection must be ensured to maintain the temperature 
class and the permissible operating temperature. The motor must not be enclosed.

 

 

Compare current type, mains voltage and frequency!  
Pay attention to the circuitry! 
Observe rated current for circuit breaker setting! 
For motors in ignition protection type 

increased safety “e” the t

E

 time must be observed! 

Connect the motor according to the terminal diagram provided in the terminal box! 

 

For earthing, there is an earth terminal on the housing or on the flanged bearing plate, depending on the de-
sign. All motors also have a protective conductor terminal inside the terminal box. Unused cable glands in 
the terminal box must be closed to protect against dust and moisture. General safety and commissioning in-
structions apply to electrical connection. The cable glands and connection screws must be approved for Ex 
atmospheres. The installation torques, sealing ranges and clamping ranges for strain relief specified by the 
gland manufacturer must always be observed. Connecting cables must be selected in accordance with DIN 
VDE 0100, taking into account the rated current and system-dependent conditions (e.g. ambient tempera-
ture, type of installation, etc. in accordance with DIN VDE 0298 or IEC/EN 60204-1). 

 

At room temperatures of more than 40°C, cables with a permissible operating temperature of at least 
90°C must be used. This also applies to motors for which the data sheet/supplement to the EU (EC) 
Type Examination Certificate refers to special requirements for cable design. 

 

When connecting motors, special care must be taken to ensure that the connections in the  
terminal box are made correctly. The nuts on the connection screws must be tightened without exerting 
force

.

  

 Creepage and clearance distances according to IEC/EN 60079-0/60079-7 must be observed.  
 
 

Tightening torques for production and testing  

Screw connections ungreased 

 

Bolt connections 

Cu / Ms 

Strength 4.6 and 5.6 

or screws made of 

Cu, Ms, Al, GG 

Strength 8.8 

- Mech. without lock 

- Busbars with lock  

Strength 8.8 

- Mech. with lock 

Dimen-

sions 

Manufactur-

ing 

[Nm] 

Testing 

[Nm] 

Manufac-

turing 

[Nm] 

Testing 

[Nm] 

Manufactur-

ing 

[Nm] 

Testing 

[Nm] 

Manufactur-

ing 

[Nm] 

Testing 

[Nm] 

Содержание W52R 355 Series

Страница 1: ...g and maintenance instructions Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage Ignition protection types Increased safety eb and ec Protection by enclosure t...

Страница 2: ...ge First edition 09 2015 11 2015 Annex 2 Update of EU Declaration of Conformity 01 2016 Change of section 5 7 to 5 8 Section 5 7 entry parts new Annex 4 new Change in the wording for the heating ca bl...

Страница 3: ...3 Risk assessment with regard to possible sparking in Ex eb IIC 3 Information about ignition protection type increased safety ec 3 1 Protective principle labelling 3 2 Risk assessment with regard to...

Страница 4: ...make changes to the product the technical data or the assembly operating and maintenance instructions without prior notice Designs technical data and illustra tions are only ever binding with written...

Страница 5: ...ng to IEC EN 60034 5 for motors used in zones 1 2 and 22 is a minimum of IP 55 For use in zone 21 the motors are designed to meet IP 65 as a minimum Only electrical machines with the approved type of...

Страница 6: ...erved 1 6 Transport and storage Any damage detected on delivery must be reported to the transport company immediately if necessary commissioning must be prevented Transport eyes attachment points are...

Страница 7: ...ain the temperature class and the permissible operating temperature The motor must not be enclosed Compare current type mains voltage and frequency Pay attention to the circuitry Observe rated current...

Страница 8: ...ions When inserting the supply cables into the terminal box make sure that the cables have strain relief The in side of the terminal boxes must be kept clean The seals must be undamaged and correctly...

Страница 9: ...eration If there are changes compared to normal operation e g increased tempera tures noises and vibrations the machine must be switched off in case of doubt The cause must be determined and the manuf...

Страница 10: ...ating manual must be observed Operation from the frequency inverter for use in zone 2 22 Ex II 3G Ex II 3D Operation with the frequency inverter is only permitted within the operating points specified...

Страница 11: ...ts are stated on the rating plate or on the EC Type Examination Certificate If the certificate number ends in an X special conditions on the EC Type Examination Certificate must be observed Electrical...

Страница 12: ...gap with squirrel cage rotors A risk assessment has been carried out by the manufacturer regarding possible sparking in the air gap of squirrel cage rotors If the sum of the factors is greater than 6...

Страница 13: ...tures of surfaces on which dust may be deposited or which may come into contact with a cloud of dust are kept below the temperatures specified in this standard All parts with electrical sparks or temp...

Страница 14: ...ox optional star point box The stator housing with feet is made of grey cast iron the bearing plates and terminal box are made of grey cast iron For high voltage motors a welded steel construction is...

Страница 15: ...connections must then be assembled with locking nuts taking into account the thickness of the plate The diameter of these through holes must be selected in accordance with DIN EN 50262 5 8 Standstill...

Страница 16: ...layers of dust lead to a temperature increase on the surface of the motor Dust deposits on motors and even their complete filling with dust must there fore be avoided as far as possible by appropriate...

Страница 17: ...t therefore be strictly observed by taking the following steps among others Limiting the total paint or resin layer thickness according to the explosion group to IIA IIB Total coating thickness 2 mm I...

Страница 18: ...ts list may be used this applies in particular to seals and connecting parts The following information is required when ordering spare parts Spare part designation Motor type Motor number 12 Disposal...

Страница 19: ...allation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 19 13 Terminal box construction...

Страница 20: ...5 4 1 5 5 1 5 6 1 5 7 1 5 8 1 5 9 1 5 10 1 5 13 1 5 15 1 6 1 1 6 5 1 7 2 1 7 4 1 Die Inbetriebnahme der unvollst ndigen Maschine ist solange untersagt bis die Konformit t der Maschine in welche die un...

Страница 21: ...Supplementary installation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 21 Annex 2...

Страница 22: ...Supplementary installation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 22...

Страница 23: ...tion of the flange is determined by the motor manufacturer Before putting the motor into operation the free volume of the motor enclosure must be purged with inert gas if necessary after ignition risk...

Страница 24: ...d on the equipment rating plate or terminal box Alternatively the number and position of the entry threads are indicated on the dimension drawing of the mo tor Unless otherwise ordered cable glands fr...

Страница 25: ...instead be approved according to IECEx or if selected by the plant operator they must be approved according to IECEx The motors are labelled as IECEx compliant For IECEx approved motors references to...

Отзывы: