Supplementary installation, operating and maintenance instructions  English 

Explosion-proof three-phase asynchronous motors with squirrel-cage rotor for high voltage 

 
 

 
815001 Edition 09.2020                                                                                                                                                                                                                                                                                                                                                                                                         
 

24 

Annex 4 
 
Information about cable glands approved for explosion protection 

The terminal boxes are designed as standard with metric threaded holes in accordance with IEC/EN 62444 
or as a special version with NPT threaded holes according to ANSI B1.20.1-1983. On delivery, they are 
sealed with plugs or ATEX-certified cable glands.  
For connection of the machine, only cable glands, cable entries and sealing plugs which are designed ac-
cording to Directive 2014/34/EU and have a minimum protection class of IP 55 or match the protection class 
of the motor must be used.  
 
For motors with i

gnition protection type “tD”, which require protection class IP 6X, the cable glands and plugs 

must be designed according to Directive 2014/34/EU and have a minimum protection class of IP 65. 
 

All unused cable entry openings must be sealed with plugs of the appropriate minimum protection 
class approved according to Directive 2014/34/EU. Existing plugs must be checked for compliance 
with this specification and replaced if necessary. 
 

The thread type is indicated on the equipment (rating plate or terminal box). 
Alternatively, the number and position of the entry threads are indicated on the dimension drawing of the mo-
tor. Unless otherwise ordered, cable glands from Jacob or Hawke are used internationally. The following 
specifications must be observed for these screw connections: 
 
Ex brass screw connection, metric thread,  
EC Certificate of Conformity DMT 99 ATEX E 016 

Thread 

Item no. 

For cable diameter 

Width across 

flats 

Installation torque 

 

 

[mm] 

[mm] 

[Nm] 

M 63x1.5 

50.663 M/EX 

32...42 

65 

20 

M 63x1.5 

50.663 M1/EX 

40...48 

65 

20 

M 75x1.5 *) 

HAWKE International 

54.5...65.3 

95 

20 

M 80x1.5 *) 

HAWKE International 

67...73 

106.4 

20 

M 90x1.5 *) 

HAWKE International 

67 … 77.6 

115 

20 

M 100x1.5 *) 

HAWKE International 

75 … 91.6 

127 

20 

*) Baseefa06ATEX0056X or IEC BAS 06.0013X. 

 
Ex-EMC brass cable gland, metric thread 
EC Certificate of Conformity DMT 99 ATEX E 016 

Thread 

Item no. 

For cable diameter 

Width across 

flats 

Installation torque 

 

 

[mm] 

[mm] 

[Nm] 

M 63x1.5 

50.663 M/EMC/EX 

32...42 

65 

20 

M 63x1.5 

50.663 M1/EMC/EX 

40...48 

65 

20 

M 75x1.5 *) 

HAWKE International 

54.5...65.3 

95 

20 

M 80x1.5 *) 

HAWKE International 

67...73 

106.4 

20 

M 90x1.5 *) 

HAWKE International 

67 … 77.6 

115 

20 

M 100x1.5 *) 

HAWKE International 

75 … 91.6 

127 

20 

*) Baseefa06ATEX0056X or IEC BAS 06.0013X. 

 
If cable glands or plugs certified according to Directive 2014/34/EU from other manufacturers are used, their 
manufacturer’s specifications must be observed. 
 
 
 
 
 
 
 
 
 
 
 
 
Certificate number: IECEx IBE 20.0025 
 

Содержание W52R 355 Series

Страница 1: ...g and maintenance instructions Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage Ignition protection types Increased safety eb and ec Protection by enclosure t...

Страница 2: ...ge First edition 09 2015 11 2015 Annex 2 Update of EU Declaration of Conformity 01 2016 Change of section 5 7 to 5 8 Section 5 7 entry parts new Annex 4 new Change in the wording for the heating ca bl...

Страница 3: ...3 Risk assessment with regard to possible sparking in Ex eb IIC 3 Information about ignition protection type increased safety ec 3 1 Protective principle labelling 3 2 Risk assessment with regard to...

Страница 4: ...make changes to the product the technical data or the assembly operating and maintenance instructions without prior notice Designs technical data and illustra tions are only ever binding with written...

Страница 5: ...ng to IEC EN 60034 5 for motors used in zones 1 2 and 22 is a minimum of IP 55 For use in zone 21 the motors are designed to meet IP 65 as a minimum Only electrical machines with the approved type of...

Страница 6: ...erved 1 6 Transport and storage Any damage detected on delivery must be reported to the transport company immediately if necessary commissioning must be prevented Transport eyes attachment points are...

Страница 7: ...ain the temperature class and the permissible operating temperature The motor must not be enclosed Compare current type mains voltage and frequency Pay attention to the circuitry Observe rated current...

Страница 8: ...ions When inserting the supply cables into the terminal box make sure that the cables have strain relief The in side of the terminal boxes must be kept clean The seals must be undamaged and correctly...

Страница 9: ...eration If there are changes compared to normal operation e g increased tempera tures noises and vibrations the machine must be switched off in case of doubt The cause must be determined and the manuf...

Страница 10: ...ating manual must be observed Operation from the frequency inverter for use in zone 2 22 Ex II 3G Ex II 3D Operation with the frequency inverter is only permitted within the operating points specified...

Страница 11: ...ts are stated on the rating plate or on the EC Type Examination Certificate If the certificate number ends in an X special conditions on the EC Type Examination Certificate must be observed Electrical...

Страница 12: ...gap with squirrel cage rotors A risk assessment has been carried out by the manufacturer regarding possible sparking in the air gap of squirrel cage rotors If the sum of the factors is greater than 6...

Страница 13: ...tures of surfaces on which dust may be deposited or which may come into contact with a cloud of dust are kept below the temperatures specified in this standard All parts with electrical sparks or temp...

Страница 14: ...ox optional star point box The stator housing with feet is made of grey cast iron the bearing plates and terminal box are made of grey cast iron For high voltage motors a welded steel construction is...

Страница 15: ...connections must then be assembled with locking nuts taking into account the thickness of the plate The diameter of these through holes must be selected in accordance with DIN EN 50262 5 8 Standstill...

Страница 16: ...layers of dust lead to a temperature increase on the surface of the motor Dust deposits on motors and even their complete filling with dust must there fore be avoided as far as possible by appropriate...

Страница 17: ...t therefore be strictly observed by taking the following steps among others Limiting the total paint or resin layer thickness according to the explosion group to IIA IIB Total coating thickness 2 mm I...

Страница 18: ...ts list may be used this applies in particular to seals and connecting parts The following information is required when ordering spare parts Spare part designation Motor type Motor number 12 Disposal...

Страница 19: ...allation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 19 13 Terminal box construction...

Страница 20: ...5 4 1 5 5 1 5 6 1 5 7 1 5 8 1 5 9 1 5 10 1 5 13 1 5 15 1 6 1 1 6 5 1 7 2 1 7 4 1 Die Inbetriebnahme der unvollst ndigen Maschine ist solange untersagt bis die Konformit t der Maschine in welche die un...

Страница 21: ...Supplementary installation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 21 Annex 2...

Страница 22: ...Supplementary installation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 22...

Страница 23: ...tion of the flange is determined by the motor manufacturer Before putting the motor into operation the free volume of the motor enclosure must be purged with inert gas if necessary after ignition risk...

Страница 24: ...d on the equipment rating plate or terminal box Alternatively the number and position of the entry threads are indicated on the dimension drawing of the mo tor Unless otherwise ordered cable glands fr...

Страница 25: ...instead be approved according to IECEx or if selected by the plant operator they must be approved according to IECEx The motors are labelled as IECEx compliant For IECEx approved motors references to...

Отзывы: