Explosion-proof three-phase asynchronous motors with squirrel-cage rotor for high voltage 

 
 

 
815001 Edition 09.2020                                                                                                                                                                                                                                                                                                                                                                                                         
 

11 

2.  Information about ignition pr

otection type increased safety “eb” 

2.1  Protective principle/labelling  

Ignition protection type in which additional measures are taken to prevent the possibility of impermissibly 
high temperatures and the occurrence of sparks or arcs during normal operation or under specified excep-
tional conditions with an increased degree of safety. 

 

Prevention of sparks and other ignition sources 

 

Enclosure at least IP54 for bare, live parts inside 

 

Enclosures at least IP44 if all live parts inside are insulated 

 

Observance of creepage and clearance distances 

 

Special attention to insulation materials and seals 

 

Temperatures of the outer and inner surfaces 

 

must be lower than the  ignition temperature both in normal operation and in the event of a fault (mo-

tor stalling) 

 

Protection devices (temperature monitoring and/or 

     

overcurrent switch with I

A

/I

N

-tE time characteristic) required for the user 

 

Frequency inverter operation see section 3 

Tests: 

 

Insulation test 

 

Temperature measurement for defined faults 

 

Additional tests for certain equipment (TMS full protection) 

 
Areas of application:  
Equipment zone 1 and 2, category 2G and 3G (Gb,Gc) 
 
Marking of the motors with EC Type Examination Certificate according to Directive 2014/34/EU (94/9/EC):  

 

CE 0637 

 II 2 G Ex eb IIC T1/T2 or T3 Gb 

 

QA certification by NB 0637 ... IBExU Freiberg 

 

For explosion-

proof motors in ignition protection type increased safety “eb” according to IEC/EN 60079–0 

and  
IEC/EN 60079

–7, the following points must be observed in particular: 

 
The greater danger in potentially explosive atmospheres requires particularly careful attention to the safety 
and commissioning instructions. Explosion-proof motors may only be used in potentially explosive atmos-
pheres in accordance with the regulations of the responsible supervisory authority. It is responsible for deter-
mining the explosion risk and zone classification. Ignition protection type, temperature class and special re-
quirements are stated on the rating plate or on the EC Type Examination Certificate. If the certificate number 
ends in an X, special conditions on the EC 

Type Examination Certificate must be observed. Electrical 

machines fall into this category, e.g. also those with ignition protection type increased safety “eb” for inverter 
operation. 

 

2.2 Information about impermissible heating 

Unless otherwise stated on the test certificate or the rating plate in connection with operating mode and toler-
ances, electrical machines are designed for continuous operation and normal, not frequently recurring starts 
during which no significant start-up heating occurs. The motors may only be used for the operating mode in-
dicated on the rating plate. If the operating mode is not indicated on the rating plate, the motors may only be 
operated in continuous operation, S1. 
The voltage and frequency limits of area A in IEC/EN 60034-1 (DIN VDE 0530, part 1) 

– voltage 

 5%, fre-

quency 

 2%, curve shape, mains symmetry 

– must be observed so that heating remains within the permissi-

ble limits. Larger deviations from the rated values can increase the heating of the electrical machine inadmis-
sibly and must be indicated on the rating plate. The motor must be protected against impermissible heating 
during start-up, e.g. with a motor protection switch, i.e. impermissible heating must be prevented in all 
phases by a current-dependent delayed circuit breaker according to DIN VDE 0660 or an equivalent device. 
The protective device must be set to the rated current. Windings in delta circuits must be protected in such a 
way that the triggers or relays are connected in series with the winding strands. Selection and setting of the 
triggers is based on the rated value of the strand current, i.e. 0.58 times the rated motor current. If a circuit of 
this sort is not possible, suitable circuit breakers, e.g. with phase failure monitoring, must be used. For pole-
changing motors, current-dependent delayed triggers or relays must be provided for each speed level and 
must be locked out from each other.  

 

With ignition protection type increased safety “eb”, the start-up is also monitored. The protective de-
vice must therefore switch off within the t

E

 time specified for the respective temperature class if the 

rotor is blocked. The requirement is met if the tripping time - which can be taken from the tripping 

Содержание W52R 355 Series

Страница 1: ...g and maintenance instructions Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage Ignition protection types Increased safety eb and ec Protection by enclosure t...

Страница 2: ...ge First edition 09 2015 11 2015 Annex 2 Update of EU Declaration of Conformity 01 2016 Change of section 5 7 to 5 8 Section 5 7 entry parts new Annex 4 new Change in the wording for the heating ca bl...

Страница 3: ...3 Risk assessment with regard to possible sparking in Ex eb IIC 3 Information about ignition protection type increased safety ec 3 1 Protective principle labelling 3 2 Risk assessment with regard to...

Страница 4: ...make changes to the product the technical data or the assembly operating and maintenance instructions without prior notice Designs technical data and illustra tions are only ever binding with written...

Страница 5: ...ng to IEC EN 60034 5 for motors used in zones 1 2 and 22 is a minimum of IP 55 For use in zone 21 the motors are designed to meet IP 65 as a minimum Only electrical machines with the approved type of...

Страница 6: ...erved 1 6 Transport and storage Any damage detected on delivery must be reported to the transport company immediately if necessary commissioning must be prevented Transport eyes attachment points are...

Страница 7: ...ain the temperature class and the permissible operating temperature The motor must not be enclosed Compare current type mains voltage and frequency Pay attention to the circuitry Observe rated current...

Страница 8: ...ions When inserting the supply cables into the terminal box make sure that the cables have strain relief The in side of the terminal boxes must be kept clean The seals must be undamaged and correctly...

Страница 9: ...eration If there are changes compared to normal operation e g increased tempera tures noises and vibrations the machine must be switched off in case of doubt The cause must be determined and the manuf...

Страница 10: ...ating manual must be observed Operation from the frequency inverter for use in zone 2 22 Ex II 3G Ex II 3D Operation with the frequency inverter is only permitted within the operating points specified...

Страница 11: ...ts are stated on the rating plate or on the EC Type Examination Certificate If the certificate number ends in an X special conditions on the EC Type Examination Certificate must be observed Electrical...

Страница 12: ...gap with squirrel cage rotors A risk assessment has been carried out by the manufacturer regarding possible sparking in the air gap of squirrel cage rotors If the sum of the factors is greater than 6...

Страница 13: ...tures of surfaces on which dust may be deposited or which may come into contact with a cloud of dust are kept below the temperatures specified in this standard All parts with electrical sparks or temp...

Страница 14: ...ox optional star point box The stator housing with feet is made of grey cast iron the bearing plates and terminal box are made of grey cast iron For high voltage motors a welded steel construction is...

Страница 15: ...connections must then be assembled with locking nuts taking into account the thickness of the plate The diameter of these through holes must be selected in accordance with DIN EN 50262 5 8 Standstill...

Страница 16: ...layers of dust lead to a temperature increase on the surface of the motor Dust deposits on motors and even their complete filling with dust must there fore be avoided as far as possible by appropriate...

Страница 17: ...t therefore be strictly observed by taking the following steps among others Limiting the total paint or resin layer thickness according to the explosion group to IIA IIB Total coating thickness 2 mm I...

Страница 18: ...ts list may be used this applies in particular to seals and connecting parts The following information is required when ordering spare parts Spare part designation Motor type Motor number 12 Disposal...

Страница 19: ...allation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 19 13 Terminal box construction...

Страница 20: ...5 4 1 5 5 1 5 6 1 5 7 1 5 8 1 5 9 1 5 10 1 5 13 1 5 15 1 6 1 1 6 5 1 7 2 1 7 4 1 Die Inbetriebnahme der unvollst ndigen Maschine ist solange untersagt bis die Konformit t der Maschine in welche die un...

Страница 21: ...Supplementary installation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 21 Annex 2...

Страница 22: ...Supplementary installation operating and maintenance instructions English Explosion proof three phase asynchronous motors with squirrel cage rotor for high voltage 815001 Edition 09 2020 22...

Страница 23: ...tion of the flange is determined by the motor manufacturer Before putting the motor into operation the free volume of the motor enclosure must be purged with inert gas if necessary after ignition risk...

Страница 24: ...d on the equipment rating plate or terminal box Alternatively the number and position of the entry threads are indicated on the dimension drawing of the mo tor Unless otherwise ordered cable glands fr...

Страница 25: ...instead be approved according to IECEx or if selected by the plant operator they must be approved according to IECEx The motors are labelled as IECEx compliant For IECEx approved motors references to...

Отзывы: