106
Separately define control terminal(X1-X6)functions. Short connect with
the terminal(COM)is valid.
Setting
value
Definition
Function description
0
Invalid(can reelection)
This port unused
1
Forward jog operation
Jog order input port. Terminal jog
orders have the highest priority
2
Reverse jog operation
3
Free stop
Free stop order input port
4
Fault reset
When breakdown, exterior reset order
input port
5
Multi steps speed control 1
The multi steps speed commands input
port. The code combination realizes 15
steps of speed; The multi steps speed
commands has priority only next to the
jog command;
6
Multi steps speed control 2
7
Multi steps speed control 3
8
Multi steps speed control 4
9
Ascend/descend
running
frequency ascending UP
Realize the ascend 、descend control
function,invalid when[E-02]or[E-03]
is set as“7”
;
10
Ascend/descend
running
frequency descending DW
11
Trilinear
operational
control
Trilinear operation control is
defined as “D(X)terminal,please
Refer to[F-08]
;
12
PID control cancel
Cancel PID operation when it is PID
control operation;then the PID given
signal is given frequency, frequency
Содержание AC60 series
Страница 1: ...Manual AC60 series frequency inverter Version V2 0...
Страница 30: ...26...
Страница 44: ...40 2 Double display keyboard cycle switch the display of monitoring parameter mode...
Страница 46: ...42 2 Double display keyboard parameter setting mode...
Страница 162: ...158 8 2 2 Over current...
Страница 163: ...159 8 2 3 Over voltage...
Страница 164: ...160 8 2 4 Supply voltage is too low...
Страница 165: ...161 8 2 5 Inner inverter over heat...
Страница 166: ...162 8 2 6 Over load...
Страница 167: ...163 8 2 7 No display 8 2 8 Motor heat...
Страница 168: ...164 8 2 9 Motor does not rotate...