150
H-69 Baud rate
Range :0 ~ 4
Factory setting:3
0:1200bps
1:2400bps
2:4800bps
3:9600bps
4:19200bps
H-70 Communication setting
frequency ratio
range:0.01~5.00
Factory setting :
1.00
The frequency instruction which is send out by superordinate machine
multiplies this parameter; The result is this machine's setting frequency.
Frequency instruction of superordination machine can be revised
proportionally.
H-71 Communication
overtime time
Range : 0.0 ~ 6500.0
second
Factory setting:
10.0 second
If the gap time between a communication and the next communication exceeds
communication overtime time, it is considered there is communication
disconnection fault , malfunction disconnection action mode is decided by the
[H-72].
H-72 RS485 communication
disconnection action mode
Range :0,1
Factory
setting:0
0:Close down
1:Maintain original state After the communication fault is detected,