126
F-59
Terminal analog input
filtering time constant
Range:0.01~5.00 second
Factory setting:
0.50 second
This is defined as the size of the input analog quantity signal filtering,
for the purpose of eliminating the interference signal. The longer filtering
time is, the stronger anti-interfere ability is, but the respond speed slow
down; The shorter filter time is, the weaker anti-interfere ability is, but
the respond speed become faster;
F-60 Output terminal ( AO1 )
selection
Range :0 ~ 7
Factory setting:
0
F-61 Output terminal ( AO2 )
selection
Range :0 ~ 7
Factory setting:
1
(AO1) output signal is voltage signal 0~10V.
(AO2) output signal is determined by[F-62].
0: Output signal close
1: Output frequency/speed