124
AS terminal input current upper limit This function defines the maximum
signal which received by the analog input terminal(AS), frequency inverter
will automatically filters the current signal whose value is higher than this
value.
AS terminal input current gain This function is used to amplify or reduce
the (AS) terminal.
F-53
Pulse input
frequency lower
limit
Range :0.0KHz~[F-54]
Factory setting:
0.0KHz
F-54
Pulse input
frequency upper
limit
Range :
[F-53]~50.0KHz
Factory setting:
10.0 KHz
F-55
Pulse input
frequency gain
Range :0.01~5.00
Factory setting:
1.00
Terminal input frequency lower limit This function defines the minimum
frequency which received by the analog input terminal(PUL). Frequency
inverter will automatically filter the frequency whose value is lower than
this value;
Terminal input frequency upper limit This function defines the maximum
frequency which received by the analog input terminal(PUL). Frequency
inverter will automatically filter the frequency whose value is higher than
this value.
Terminal input frequency gain This function is used to amplify or reduce
the (PUL)terminal input signal.
F-56
Terminal input lower
limit
setting
frequency
Range :0.00Hz~[F-57]
Factory
setting:0.00Hz
Содержание AC60 series
Страница 1: ...Manual AC60 series frequency inverter Version V2 0...
Страница 30: ...26...
Страница 44: ...40 2 Double display keyboard cycle switch the display of monitoring parameter mode...
Страница 46: ...42 2 Double display keyboard parameter setting mode...
Страница 162: ...158 8 2 2 Over current...
Страница 163: ...159 8 2 3 Over voltage...
Страница 164: ...160 8 2 4 Supply voltage is too low...
Страница 165: ...161 8 2 5 Inner inverter over heat...
Страница 166: ...162 8 2 6 Over load...
Страница 167: ...163 8 2 7 No display 8 2 8 Motor heat...
Страница 168: ...164 8 2 9 Motor does not rotate...