69
OFF
ON
ON
OFF
RS485 communication
port
OFF
ON
ON
ON
ascend 、descend
control
ON
OFF
OFF
OFF
Normal PID operation
ON
OFF
OFF
ON
constant pressure
control
ON
OFF
ON
OFF
Program run
ON
OFF
ON
ON
swing frequency
operation
Tips: Valid frequency selection terminals combinations are 0 to 11 (10
digits). If not in this range, frequency inverter output 0 frequency;
"OFF" in the table said corresponding terminal and (COM) disconnected.
"ON" said corresponding terminal and (COM) short connect.
E-03
Frequency given
auxiliary channel
selection
range:0 ~ 10
Factory
setting:0
[E-03]is use to select the auxiliary input channels of the give frequency.
If you need more details about the combination method of the auxiliary
channel and the main channel, please refer to [E-05].
0:Keyboard number given The given frequency of the auxiliary channel is
determined and amended by the Up/down key on the keyboard or parameters
[E-16]
1 Keyboard potentiometer The given frequency of the auxiliary channel is
determined and amended by the potentiometer on the keyboard.
2:Terminal VS1 voltage 0~10V The given frequency of the auxiliary
channel is determined and amended by the control panel analog quantity
input terminal (VS1).
3:Terminal AS current 4 ~ 20mA The given frequency of the auxiliary
channel is determined and amended by the control panel analog quantity
Содержание AC60 series
Страница 1: ...Manual AC60 series frequency inverter Version V2 0...
Страница 30: ...26...
Страница 44: ...40 2 Double display keyboard cycle switch the display of monitoring parameter mode...
Страница 46: ...42 2 Double display keyboard parameter setting mode...
Страница 162: ...158 8 2 2 Over current...
Страница 163: ...159 8 2 3 Over voltage...
Страница 164: ...160 8 2 4 Supply voltage is too low...
Страница 165: ...161 8 2 5 Inner inverter over heat...
Страница 166: ...162 8 2 6 Over load...
Страница 167: ...163 8 2 7 No display 8 2 8 Motor heat...
Страница 168: ...164 8 2 9 Motor does not rotate...