68
with "0" frequency when arriving at that section speed.
Program running and multi step speed operation are designed to achieve
inverter variable-speed operation under a certain laws. Among the multi step
operation, multi steps speed switch and running direction change are
achieved through the different combination of exterior multi steps speed
control terminal(such as X1、X2、X3、X4)and(FWD)
、
(REV)with(COM). Not
only a circle of multi step frequency can be defined in the function parameter,
but also multi step frequency operation time、direction and circulating mode
can be defined in the function parameter.
11:Swing frequency run Output frequency periodically changes by pre-set
dece&acce time. This function is particularly compliant to the system of the
textile industry in which the rotational speed changes according to the
diameter difference between the before and behind copper tube.
12:Terminal selection The main channel for given frequency is selected
by the frequency selection terminal, refer to the parameter[F-01~F-06];
Terminal mode and frequency setting channel corresponding relationship are
shown in the follow diagram:
Frequency
Setting
selection
terminal
4
Frequency
Setting
selection
terminal 3
Frequency
Setting
selection
terminal 2
Frequency
Setting
selection
terminal 1
Frequency setting
channel
OFF
OFF
OFF
OFF
Keyboard number
setting
OFF
OFF
OFF
ON
keyboard potentiometer
OFF
OFF
ON
OFF
terminal(VS1)voltage
signal
OFF
OFF
ON
ON
terminal(AS)current
signal
OFF
ON
OFF
OFF
terminal(VS2)voltage
signal
OFF
ON
OFF
ON
Terminal pulse signal
Содержание AC60 series
Страница 1: ...Manual AC60 series frequency inverter Version V2 0...
Страница 30: ...26...
Страница 44: ...40 2 Double display keyboard cycle switch the display of monitoring parameter mode...
Страница 46: ...42 2 Double display keyboard parameter setting mode...
Страница 162: ...158 8 2 2 Over current...
Страница 163: ...159 8 2 3 Over voltage...
Страница 164: ...160 8 2 4 Supply voltage is too low...
Страница 165: ...161 8 2 5 Inner inverter over heat...
Страница 166: ...162 8 2 6 Over load...
Страница 167: ...163 8 2 7 No display 8 2 8 Motor heat...
Страница 168: ...164 8 2 9 Motor does not rotate...