73
0:Reverse This key is defined as reverse key(at this moment ,keyboard
functional indicator REV / JOG do not light). When the operation order
given channel is set as keyboard control, press this key ,frequency
inverter will reverse operate.
1:Jog This key is defined as jog key(at this moment ,keyboard functional
indicator REV / JOG light. When the operation given channel is set as
keyboard control , press this key ,frequency inverter will jog operate.
E-09
Maximum frequency
Range:0.50~400.0Hz
Factory
setting:50.0
E-10
Upper
frequency
limit
Range:Lower frequency limit
~Maximum frequency
Factory
setting:50.0
E-11
Lower
frequency
limit
Range:0.00~Upper frequency
limit
Factory
setting:0.00
E-12
Lower
frequency
limit
operation
mode
Range:0,1
Factory
setting:0
Maximum frequency is the highest frequency that inverter allows to set,
as well as the basis of acceleration and deceleration time setting.
Upper frequency limit is the frequency inverter output frequency upper
limit value which is set base on the highest speed of mechanical machine.
When the given frequency is higher than limit, actual running frequency
is upper frequency limit.
Lower frequency limit is the lower limit value of the frequency inverter
output frequency. When the given frequency is lower than the lower limit, the
actual running frequency is determined by the [E-12].
Содержание AC60 series
Страница 1: ...Manual AC60 series frequency inverter Version V2 0...
Страница 30: ...26...
Страница 44: ...40 2 Double display keyboard cycle switch the display of monitoring parameter mode...
Страница 46: ...42 2 Double display keyboard parameter setting mode...
Страница 162: ...158 8 2 2 Over current...
Страница 163: ...159 8 2 3 Over voltage...
Страница 164: ...160 8 2 4 Supply voltage is too low...
Страница 165: ...161 8 2 5 Inner inverter over heat...
Страница 166: ...162 8 2 6 Over load...
Страница 167: ...163 8 2 7 No display 8 2 8 Motor heat...
Страница 168: ...164 8 2 9 Motor does not rotate...