91
Tips: users should be cautious to consider the start characteristic of the
mechanical devices during the manipulation. In occasions where it can not
start with load or it must alarm immediately while frequency inverter has no
output, please think carefully before use this function.
E-45 Warm-up time
Range :0.0~6500 second
Factory
setting:0.0second
Begine to time while the frequency inverter is well prepared to transmit
power. After reaching to the warming-up Time, frequency inverter can accept
the rotation control order. After electrify, start to backward count in unit
of sec on the screen.
E-46 Operation
direction
selection
Range :0~2
Factory
setting:0
0: Consistent with the default direction Actual rotation direction is
the same with the requirement. The actual direction will not be adjusted;
1: Opposite to the default direction Actual rotation direction is
opposite to the requirement. The actual direction will be adjusted;
2: Prohibit the reverse operation When this parameter is set as prohibition,
all the reverse order of the operation order channel(operation panel、
exterior terminal、RS485 communication、bipolar VS2 and program running)
are invalid.
Attention: 1、when choose the reverse prohibition, if the bipolar control
receives the reverse frequency order, frequency inverter will operate as
“0”frequency,it is the same in the program operational control, if the
setting direction of a certain step speed is reverse, frequency inverter will
operate as “0”frequency in this section.
2、All the reverse order will automatically switch to operation
Содержание AC60 series
Страница 1: ...Manual AC60 series frequency inverter Version V2 0...
Страница 30: ...26...
Страница 44: ...40 2 Double display keyboard cycle switch the display of monitoring parameter mode...
Страница 46: ...42 2 Double display keyboard parameter setting mode...
Страница 162: ...158 8 2 2 Over current...
Страница 163: ...159 8 2 3 Over voltage...
Страница 164: ...160 8 2 4 Supply voltage is too low...
Страница 165: ...161 8 2 5 Inner inverter over heat...
Страница 166: ...162 8 2 6 Over load...
Страница 167: ...163 8 2 7 No display 8 2 8 Motor heat...
Страница 168: ...164 8 2 9 Motor does not rotate...