Initial Setup Of The Console Using Workflow Wizard
Setup>Pumps and Lines>PLLD
43
Setup>Pumps and Lines>PLLD
0.2 gph (0.76lph) Line Leak Test
Touch to select the scheduling frequency of the 0.2 gph (0.76lph) periodic
tests:
Disabled
- No
m
anual, repetitive, or
m
onthly 0.2 gph (0.76lph) testing is
allowed. This is the default.
Repetitive
- After a dispense, a 3.0 gph (11.3lph) test is run, followed by a
0.2 gph (0.76lph) test. The test blockout period (the
Precision Test Delay
ps and Lines>All PLLD”) is then observed. Following the
test blockout period, the test sequence repeats after the next dispense.
NOTE: If the 0.1 gph (0.3 lph) test is set for
Repetitive
, this test
m
ust also
be set to Repetitive. This selection also enables
m
anual 0.2 gph (0.76lph)
tests to run when
m
anually started.
Monthly
- The test is scheduled at the beginning of a new
m
onth and
re
m
ains scheduled until a test is passed.
Manual
- 0.2 gph (0.76lph) tests run only when
m
anually started in Diagnos-
tics>PLLD>Manual Tests
0.1 gph (0.38lph) Line Leak Test
Touch to select the scheduling frequency of the 0.1 gph (0.38lph) precision
tests.
Disabled
- No
m
anual or auto
m
atic 0.1 gph (0.3 lph) testing is allowed. This
is the default.
Repetitive
- After a dispense, a 3.0 gph (11.3lph) test is run, a 0.2 gph
(0.76lph) test is run, followed by the 0.1 gph (0.38lph) test. The test blockout
period (the
Precision Test Delay
is then observed. Following the test blockout period, the test sequence
repeats after the next dispense. This selection also enables
m
anual 0.1 gph
(0.38lph) testing tests to run when
m
anually started.
Auto
- The 0.1 gph (0.38lph) test is auto
m
atically scheduled ro tun 6
m
onths
after the last passed 0.1 gph (0.38lph) test. This setting also gives you the
option to run the Passive 0.1 gph (0.38lph) Line Leak Test.
Manual
- 0.1 gph (0.38lph) test runs only when
m
anually started in Diagnos-
tics>PLLD>Manual Tests.
Passive 0.1 gph (0.38lph) Line Leak Test
[only available if the pipe type is user-defined and the 0.1 gph (0.38lph) Line
Leak Test is set to
Auto
].
Enables a 0.1 gph (0.38lph) test to run after a passed 0.2 gph (0.76lph) test
without the 0.1 gph (0.38lph) test being actively scheduled. If the 0.1 gph
(0.38lph) test also passes, you are notified in Diagnostics>PLLD> 0.1 GPH
Tests. If it fails, there is no notification of the passive 0.1 gph (0.38lph) test.
Allowable selections: Yes, No (default is No).
Shutdown Rate
The line is shut down if a specified or less precise PLLD test fails. For exa
m
-
ple, if you set the shutdown rate for 0.2 gph (0.76lph), the line will shut down
if it fails both the 3.0 gph (11.3lph) test and the 0.2 gph (0.76lph) test.
Allowable selections: 3.0 gph (11.3lph), 0.2 gph (0.76lph), 0.1gph (0.38lph),
or None (default is 3.0 gph (11.3lph).
Low Pressure Shutoff
If a low pressure is detected during dispense, the Low Pressure Alar
m
is
triggered. The dispenser also halts dispensing if this field is enabled and the
pressure is less than the
Low Pressure Shutoff Value
field below.
Allowable selections: Disabled, Enabled (default is Disabled).
Low Pressure Shutoff Value
If a low pressure is detected during dispense, a low pressure alar
m
is trig-
gered. The dispenser also halts dispensing if the pressure is lower than the
value in this field.
Allowable selections: 0 to 25 psi (0 to 172kPa)
Default: 0.0
Continuous Handle Timeout
If the dispenser handle re
m
ains off the hook for the period of ti
m
e entered in
this field, the line is shut down by the console.
Allowable selections: 1 to 16 hours. Default: 16 hours
Fuel Out Limit
If the tank product level is below the li
m
it entered in this field, the Fuel Out
Alar
m
is triggered.
Allowable selections: 0.00 to 15.00 in (0.00 to 381.00
mm
). Default: 10.00 in
(254
mm
).
Altitude Pressure Offset
Allows you to set an altitude pressure adjust
m
ent for the absolute pressure
transducer of plus or
m
inus 5psi.
Allowable selections: -5.0 to 5.0. Default: 0.0.