Initial Setup Of The Console Using Workflow Wizard
Setup>Tank>Environmental Test
31
Setup>Tank>Environmental Test
- Concluded
Leak Min. Annual (% Full Volume)
Touch to enter a
m
ini
m
u
m
tank volu
m
e required to record a valid annual test
(value reflects federal, state, and local require
m
ents)
• If the syste
m
has enough data to declare a Passed test result before the
test duration ends, it reports it i
mm
ediately and ends the test.
• If not, it runs the entire duration of the test before reporting a Failed or
Invalid result.
Early Stop
Touch to enable or disable Early Stop. When enabled, the following occurs:
Starting the Test
- Syste
m
checks for these unrecoverable conditions, and
if it encounters any one of the
m
, it reports an Invalid test result i
mm
ediately
and ends the test:
• Fuel level is less than the Leak Min. Periodic (% full Volu
m
e) value (0.2 gph
test rate) or the Leak Min. Annual (0.1 gph test rate) value.
• Less than 8 hours has passed fro
m
the ti
m
e of a delivery for a Standard
test, or 5 hours fro
m
the delivery for a Quick test.
• The product te
m
perature is less than 0°F (-17.6°C) or
m
ore than +100°F
(+37.4°C).
• The fuel level is too low.
Running the Test
- If the syste
m
does not encounter any unrecoverable
conditions (as listed above), it begins the test and does the following:
• If the syste
m
has enough data to declare a Passed test result before the
test duration ends, it reports it i
mm
ediately and ends the test.
• If not, it runs the entire duration of the test before reporting a Failed or
Invalid result.
Tank Test Notify
Touch to enable or disable Tank Test Notify. When enabled, a Tank Test Notify
m
essage is posted in the alar
m
indicator screen during a periodic test (used
in conjunction with Tank Test Siphon Break field below)
Tank Test Siphon Break
To properly perfor
m
an in-tank leak test on siphon
m
anifolded tanks, the fol-
lowing is required:
• A siphon break solenoid valve is installed between the two siphon
m
ani-
folded tanks.
• Both the Tank Test Notify field (above) and the Tank Test Siphon Break field
are enabled.
• A relay
m
ust be progra
mm
ed to perfor
m
the siphon break. The Tank Notify
condition is assigned to this relay (that controls the siphon break solenoid
valve) in Setup>Auto
m
atic Events>Device Tasks
.
CSLD
Gross Test Auto-Confirm
Enables or disables the ability of the console to require two failed Gross
Tests [(1.5 gph (5.8 lph)] before it considers the test a failure.
NOTE:
When enabled, this feature
m
ay reduce false alar
m
s.
Probability of Detection
Touch to enter a probability of detection rate (95% or 99%). This value rep-
resents the detection percentage. So
m
e locations require a 99% probability
of detection (with a false alar
m
rate of 1%).
NOTE:
If Custo
m
appears in this field, the console is using a special value
that should not be changed.
Climate Factor
Touch to enter a cli
m
ate factor
•
Moderate
- for
m
ost situations
•
Extreme
- when a tank exhibits consistent, extre
m
e vapor loss due to
fuel evaporation.
NOTE
:
If this is set incorrectly, it
m
ay cause false Leak Alar
m
s with
nor
m
al CSLD leak detection.
CSLD Evap. Compensation
[Field available only if the Cli
m
ate Factor field is set to Extre
m
e]
Enables or disables the CSLD Evaporation Co
m
pensation feature which is
used on tanks that exhibit evidence of consistent, extre
m
e vapor loss due to
fuel evaporation that can otherwise lead to false Leak Alar
m
s with nor
m
al
CSLD leak detection.
NOTE:
This field should only be enabled after consulting a Veeder-
Root field engineer or technical support representative.
State II Vapor Recovery
[Field available only if the Cli
m
ate Factor field is set to Extre
m
e and CSLD
Evap. Co
m
pensation field is Enabled]
If the site incorporates the Stage II Vapor Recovery feature (which recovers
vapors during the vehicle refueling process), this field should be set to
Enabled
.