Initial Setup Of The Console Using Workflow Wizard
Setup>Devices
20
Setup>Devices
- Continued
PROBE SETUP
Set up each probe being
m
onitored before selecting the next device type.
Configured
Touch the radio button to enable or disable configuration of the selected
probe.
NOTES:
•
Do not enable probe configuration until its address is assigned!
• Once enabled, do not disable a probe if it is assigned to a tank. You
m
ust
first unassign the probe fro
m
the tank before the probe can be disabled.
(see Setup > Tank > General).
Address
Touch and select the address of this probe.
Label
Touch to enter a description of this probe (up to 20 alphanu
m
eric characters)
that will appear on the console screens and in reports.
Serial Number
[Read Only] Console auto-detected serial nu
m
ber of this device.
Type
[Read Only] Console auto-detected type of this device.
Float Type
Installed Mag probe float type (the console will display only the applicable
float size options for this device). For exa
m
ple, depending on the probe
installed the float sizes below could display in the drop down list:
NOTES:
• Only circuit codes D004, D005 and D006 are allowed to set the float type to
4.0 in phase separation.
• If the probe is changed and the previous float is supported by the new
probe, the float assign
m
ent will re
m
ain the sa
m
e. Otherwise the default
float will be assigned to the new probe.
• Only select
Custom
if the literature that was shipped with probe float kit
specifically states that you
m
ust choose this Float Type. Currently only
three
m
ag probes use Custo
m
Float Types: Che
m
-ISO
m
ag probes, LPG-ISO
m
ag probes and the Mag-FLEX probe with low level water floats.
When
Custom
float type is selected, the Fuel Offset, Water Offset, Water
Mini
m
u
m
and Invalid Fuel para
m
eter fields below are enabled for edit.
Refer to the appropriate installation kit
m
anual for these entries (see
Fuel Offset -
Touch to enter the Fuel Offset value listed in the appropriate
kit
m
anual (577013-770, 577013-773 or 577014-056).
Water Offset
(Mag-FLEX probes with Low Level Water Float only) -
Touch to enter the Water Offset value listed in the 577014-056
m
anual.
Water Minimum
(Mag-FLEX probes with Low Level Water Float only) -
Touch to enter the Water Mini
m
u
m
value listed in the 577014-056
m
anual.
Invalid Fuel -
Touch to enter the Invalid Fuel value listed in the appropri-
ate kit
m
anual (577013-770, 577013-773 or 577014-056).
Density Code
This field stores specifications for a density probe. It
m
ust be exactly 14
characters, and is co
m
posed of four parts as described below:
The density code has the following for
m
at: FGGGGGGMMMMDDD, e.g.,
B7053686719512, and is i
m
pressed in the float body (see i
m
age below).
Where:
F
= Fuel Type: A for gasoline and B for diesel.
Using the exa
m
ple density code above: B = Diesel,
G
= Gauss
The last two digits are the gauss readings for each
m
agnet in the den-
sity float. The prefix is always 7 and is o
m
itted fro
m
the density code.
Using the exa
m
ple density code above:
70 Gauss = 77.0 for top
m
agnet in gra
m
s
53 Gauss = 75.3 for
m
iddle
m
agnet in gra
m
s
68 Gauss = 76.8 for botto
m
m
agnet in gra
m
s
M
= Mass
The last four digits of the
m
ass of the float. The prefix is always 1 and is
o
m
itted fro
m
the density code.
Using the exa
m
ple density code above:
6719 = Mass of 16.719 gra
m
s
D
= Density of the float
The prefix is dependent on the fuel type and is o
m
itted fro
m
the density
code. A = 7 (gasoline) and B = 8 (diesel).
Using the exa
m
ple density code above:
512 = density of 851.2 kg/
m
3
for a fuel type of diesel.
NOTE: If you change the Density Code, the Density Offset History is
cleared and current Density Offset is set to zero. See Diagnostics>
Probe>Density Offset screen for details on console density values.
Density Float Serial Number
Touch this field to enter the density float’s serial nu
m
ber.
NOTE: if you change the density float serial nu
m
ber, the Density Offset
History is cleared and the current Density Offset is reset to zero.
The density float serial nu
m
ber has the following for
m
at - yywwxxxx,
e.g., 13240161, and is i
m
pressed in the float body (see i
m
age below).
Where;
YY
= the last two digits of the year it was
m
anufactured’
WW
= the nu
m
ber of the week it was
m
anufactured,
XXXX
= a unique integer for the density float
•
4.0
in
•
4.0
in
phase
separation
•
3.0
in
•
2.0
in
non
‐
density
water
float
•
2.0
in
standard
‐
standard
density
water
float
(1.5
inch
minimum
water
level)
•
2.0
in
low
water
‐
low
water
density
water
float
(1
inch
minimum
water
level)
•
Custom
B7053686719512
S/N: 13240161
Exa
m
ple De
n
sity Code
Exa
m
ple Se
r
ial Nu
m
be