Initial Setup Of The Console Using Workflow Wizard
Setup>Pumps and Lines>All PLLD
45
Setup>Pumps and Lines>All PLLD
This screen lets you setup test para
m
eters for all pressurized line leak detectors.
Line Re-Enable Method
Deter
m
ines what conditions allow you to re-enable the line.
Allowable selections:
• Pass Line Test - The line
m
ust pass the test in order to be enabled.
• Alar
m
Acknowledge - The line can be enabled after the alar
m
is acknowledged.
Periodic Test Warnings
Touch to enable or disable the Periodic Test Needed Warning/Alar
m
which infor
m
s you that
a line will soon be out of co
m
pliance because a Periodic test was not co
m
pleted within the
required ti
m
e. This lets you stop dispensing fro
m
the line until a Periodic test has been co
m
-
pleted.
Days before Periodic Warning
The nu
m
ber of days before the Periodic Test Alar
m
Warning is triggered.
Allowable selection: 0 - 30 days (default is 25 days).
Days before Periodic Alarm
The nu
m
ber of days before the Periodic Test Needed Alar
m
is triggered.
Allowable selection: 0 - 30 days (default is 30 days).
Annual Test Needed Warnings
Touch to enable or disable the Annual Test Needed Warnings which infor
m
s you that a line
will soon be out of co
m
pliance because an Annual test was not co
m
pleted within the
required ti
m
e. This lets you stop dispensing fro
m
the line until an Annual test is co
m
pleted.
Days before Annual Warning
The nu
m
ber of days before the Annual Test Needed Warning is triggered.
Allowable selection: 0 - 365 days (default is 355).
Days before Annual Alarm
The nu
m
ber of days before the Annual Test Needed Alar
m
is triggered.
Allowable selection: 0 - 365 days (default is 365)
Precision Test Delay (hours)
The nu
m
ber of hours between a passed periodic or annual
test and running the next line test(s).
NOTE: In previous TLS consoles, this was referred to as Pre-
cision Test Duration.
Allowable selection: 12 to 744 hours
NOTE: When CSLD is enabled for the tank assigned to the
line, a
m
ini
m
u
m
value of 60 hours is used internally when the
precision test delay value is less than 60.
0.1 gph (0.38 lph) Line Test Auto Confirm
Touch to enable or disable the ability of the console to evalu-
ate several 0.1 gph (0.38 lph) line tests before a result is
posted. Enabling Auto Confir
m
reduces the risk of false test
results, but it extends the ti
m
e that it
m
ay take to post
results.
0.2 gph (0.76 lph) Line Test Auto Confirm
Touch to enable or disable the ability of the console to evalu-
ate several 0.2 gph (0.76 lph) line tests before a result is
posted. Enabling Auto Confir
m
reduces the risk of false test
results, but it extends the ti
m
e that it
m
ay take to post
results.
See the Actions>Help>Understanding Regulatory Co
m
pli-
ance In-Tank Leak Tests topic for
m
ore infor
m
ation.