50
•
vacon
parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
8.1 Quick setup parameters (Virtual menu, shows when par. 17.2 = 1)
Code
Parameter
Min
Max
Unit
Default
ID
Note
Motor nominal
voltage
180
690
V
Varies
110
Check rating plate on the
motor.
Motor nominal
frequency
30,00 320,00
Hz
50,00 /
60,00
111
Check rating plate on the
motor.
Motor nominal
speed
30
20000
rpm
1440 /
1720
112
Default applies for a 4-
pole motor.
Motor nominal
current
0,2 x
I
Nunit
2,0 x
I
Nunit
A
I
Nunit
113
Check rating plate on the
motor.
Motor cos
(Power Factor)
0,30
1,00
0,85
120
Check rating plate on the
motor.
0,2 x
I
Nunit
2.0 x
I
Nunit
A
1.5 x
I
Nunit
107
Maximum motor current
0
1
0
109
0
= Not used
1
= Used
P2.1
0
1
0
172
0
= I / O terminal
1
= Fieldbus
0
1
0
505
0
= Ramp
1
= Flying start
0
1
0
506
0
= Coasting
1
= Ramp
Min frequency
0,00
P3.2
Hz
0,00
101
Minimum freq reference
Max frequency
P3.1 320,00
Hz
50,00 /
60,00
102
Maximum freq refer-
ence
P3.3
1
6
4
117
1
= Preset Speeds 0-7
2
= Keypad
3
= Fieldbus
4
= AI1
5
= AI2
6
= PI
P3.4
P3.1
P3.2
Hz
5,00
124
Activated by digital
inputs
P3.5
P3.1
P3.2
Hz
10,00
105
Activated by digital
inputs
P3.6
P3.1
P3.2
Hz
15,00
106
Activated by digital
inputs
P3.7
P3.1
P3.2
Hz
20,00
126
Activated by digital
inputs
Table 8.1: Quick setup parameters
P1.1
P1.2
P1.3
P1.4
P1.5
i
i
i
i
i
i
i
i
i
i
P1.7
P1.15
P2.2
P2.3
P3.1
P3.2
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...