26
•
vacon
installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
3
Frame
Type
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI2
0001-0004
20
2*2.5+2.5
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0005
32
2*6+6
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
Table 3.5: Cable and fuse sizes for Vacon 10, 115 V, 1~
Frame
Type
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1
0001-0003
10
2*1.5+1.5
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI2
0004-0007
20
2*2.5+2.5
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0009
32
2*6+6
3*1.5+1.5
1.5-6
1.5-6
0.5-1.5
0.5-1.5
Table 3.6: Cable and fuse sizes for Vacon 10, 208 - 240 V, 1~
Frame
Type
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1
0001-0003
6
3*1.5+1.5
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI2
0004-0007
10
3*1.5+1.5
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0011
20
3*2.5+2.5
3*2.5+2.5
1.5-6
1.5-6
0.5-1.5
0.5-1.5
Table 3.7: Cable and fuse sizes for Vacon 10, 208 - 240 V, 3~
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...