9.13.3 Modbus process data
Process data is an address area for fieldbus control. Fieldbus control is active when
the value of parameter 2.1 (Control place) is 3 (= fieldbus). The content of the process
data has been determined in the application. The following tables present the proc-
ess data contents in the General Purpose Application.
Note! 2004 can set as PI Control Reference by setting P15.1(Setpoint se-
lection) or 2005 can be set as PI Actual value by setting P15.4(Feed-
back value selection)!
ID
Modbus register
Name
Scale
Type
2101
32101, 42101
FB Status Word
-
Binary coded
2102
32102, 42102
FB General Status Word
-
Binary coded
2103
32103, 42103
FB Actual Speed
0,01
%
2104
32104, 42104
Output frequency
0.01
+/- Hz
2105
32105, 42105
Motor speed
1
+/- Rpm
2106
32106, 42106
Motor current
0.01
A
2107
32107, 42107
Motor torque
0,1
+/- % (of nomi-
nal)
2108
32108, 42108
Motor power
0,1
+/- % (of nomi-
nal)
2109
32109, 42109
Motor voltage
0,1
V
2110
32110, 42110
DC link voltage
1
V
2111
32111, 42111
Active fault code
1
-
Table 9.4: Output process data
ID
Modbus register
Name
Scale
Type
2001
32001, 42001
FB Control Word
-
Binary coded
2002
32002, 42002
FB General Control Word
-
Binary coded
2003
32003, 42003
FB Speed Reference
0,01
%
2004
32004, 42004
Programmable by P15.1
2005
32005, 42005
Programmable by P15.4
2006
32006, 42006
-
-
-
2007
32007, 42007
-
-
-
2008
32008, 42008
-
-
-
2009
32009, 42009
-
-
-
2010
32010, 42010
-
-
-
2011
32011, 42011
-
-
-
Table 9.5: Input process data
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...