52
•
vacon
parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
8.2 Motor settings (Control panel: Menu PAR -> P1)
Code
Parameter
Min
Max
Unit
Default
ID
Note
Motor nominal
voltage
180
690
V
Varies
110
Check rating plate on the
motor
Motor nominal fre-
quency
30,00 320,00
Hz
50,00 /
60,00
111
Check rating plate on the
motor
Motor nominal
speed
30
20000
rpm
1440 /
1720
112
Default applies for a 4-pole
motor.
Motor nominal
current
0,2 x
I
Nunit
2,0 x
I
Nunit
A
I
Nunit
113
Check rating plate on the
motor
Motor cos
(Power Factor)
0,30
1,00
0,85
120
Check rating plate on the
motor
Motor type
0
1
0
650
0
= Induction
1
= Permanent magnet
0,2 x
I
Nunit
2.0 x
I
Nunit
A
1.5 x
I
Nunit
107 Maximum motor current
0
1
0
600
0
= Frequency control
1
= Open loop speed control
0
2
0
108
0
= Linear
1
= Quadratic
2
= Programmable
8,00
320,00
Hz
50,00 /
60,00
602
Field weakening point fre-
quency
10,00 200,00
%
100,00
603
Voltage at field weakening
point as % of U
nmot
0,00
P1.10
Hz
50,00 /
60,00
604
Mid point frequency for
programmable U / f
0,00
P1.11
%
100,00
605
Mid point voltage for pro-
grammable U / f as % of
U
nmot
0,00
40,00
%
Varies
606
Voltage at 0 Hz as % of
U
nmot
0
1
0
109
0
= Disabled
1
= Enabled
1,5
16,0
kHz
4,0 / 2,0
601
PWM frequency. If values
are higher than default,
reduce the current capacity
0
2
0
504
0
= Disabled
1
= Enabled: Always
2
= Run state
Table 8.2: Motor settings
P1.1
P1.2
P1.3
i
i
i
i
i
i
i
i
i
i
i
P1.4
P1.5
P1.6
P1.7
P1.8
P1.9
P1.10
P1.11
P1.12
P1.13
P1.14
P1.15
P1.16
P1.17
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...